Fire Safety Guide for
Building Owners and
Operators
Guide for persons having control under
Section 18(2) of the Fire Services Acts 1981
and 2003
August 2023
Prepared by the Department of
Housing, Local Government and Heritage
gov.ie
i
Table of Contents
1 Introduction .......................................................................................................... 1
1.1 Special Hazards ............................................................................................ 3
2 Interpretation........................................................................................................ 4
3 Persons Having Control (PHC) ............................................................................ 5
3.1 Competent Persons ...................................................................................... 6
4 Requirements under the Fire Services Acts 1981 and 2003 ................................ 8
4.1 Section 18(1) ................................................................................................. 9
4.2 Section 18(2) ............................................................................................... 10
4.3 Section 18(3) ............................................................................................... 14
4.4 Inspection and Enforcement........................................................................ 14
4.5 Section 20(5) ............................................................................................... 15
5 Main Duties for Persons having Control ............................................................ 16
5.1 Fire Safety Programme ............................................................................... 16
5.2 Fire Prevention ............................................................................................ 17
5.2.1 Rubbish and Waste .............................................................................. 17
5.2.2 Smoking ................................................................................................ 17
5.2.3 Storage of Gas Cylinders/Cartridges .................................................... 17
5.2.4 Storage of flammable, explosive or potentially explosive substance Gas
Cylinders/Cartridges .......................................................................................... 18
5.2.5 Electrical Installations and Appliances .................................................. 18
5.2.6 Heating and Ventilation Systems .......................................................... 18
5.2.7 Kitchens ................................................................................................ 19
5.2.8 Laundries .............................................................................................. 19
5.2.9 Flammable Liquids ............................................................................... 20
5.2.10 Hot Work ........................................................................................... 20
5.3 Staff Training ............................................................................................... 20
ii
5.3.1 Fire Emergency Plan ............................................................................ 21
5.3.2 Evacuation Drills ................................................................................... 22
5.3.3 Fire Safety Instructions for Occupants .................................................. 22
5.4 Escape Routes ............................................................................................ 22
5.4.1 Escape routes in Places of Assembly ................................................... 23
Regulation 4 ....................................................................................................... 25
5.4.2 Overcrowding ....................................................................................... 25
5.5 Liaison with the Fire Authority and Assisting the Fire Service ..................... 26
5.5.1 Liaison with the Fire Authority ............................................................... 26
5.5.1 Assisting the Fire Service ..................................................................... 26
5.5.2 Plan of Premises .................................................................................. 27
5.6 Fire Safety Register Record Keeping ....................................................... 27
5.6.1 Fire Safety Register .............................................................................. 27
5.6.2 Additional Information ........................................................................... 30
6 Fire Safety Maintenance and Testing ................................................................ 31
6.1 Fire Safety Systems: Testing, Inspection and Maintenance ........................ 31
6.2 Fire Detection and Alarm Systems .............................................................. 33
6.3 Emergency Lighting System........................................................................ 34
6.4 Fire Doors ................................................................................................... 36
6.5 Fire Mains: Risers/Fallers ........................................................................... 39
6.6 Firefighting Shafts and Lifts ......................................................................... 40
6.7 First Aid Firefighting Equipment, including Hose Reels ............................... 41
6.8 Smoke Control Systems .............................................................................. 43
6.8.1 Stairway Smoke Control ....................................................................... 43
6.8.2 Smoke Control in Larger more Complex Buildings ............................... 44
6.8.3 Smoke Clearance Systems in Enclosed Car Parks .............................. 44
iii
6.9 Sprinkler Systems ....................................................................................... 47
6.10 Doors on Escape routes, Final Exit Doors ............................................... 47
6.11 Maintenance of Private Fire Hydrants and Water Supplies ...................... 48
6.12 Maintenance of Compartmentation (Fire Stopping) ................................. 49
7 Buildings containing Flats/ Apartments .............................................................. 52
7.1 Fire Detection and Alarm Systems .............................................................. 53
7.2 Emergency Lighting System in Buildings with Open Shared Balcony Egress
54
7.3 Sprinkler Systems ....................................................................................... 54
7.4 Smoke Control ............................................................................................ 54
7.5 Evacuation procedures ............................................................................... 56
7.6 Flat/Apartment Doors .................................................................................. 57
7.7 Building Layout ............................................................................................ 57
8 Recommended Routine Maintenance Schedules .............................................. 59
Appendix A. Referenced Standards ...................................................................... 76
Appendix B. Legislation ......................................................................................... 78
Appendix C. Other Publications ............................................................................. 79
Appendix D. Technical Guidance Documents ....................................................... 80
Appendix E. Management Responsibilities - Exemplar Premise (Informative) ...... 83
Appendix F. Requirements for Landlords .............................................................. 84
Appendix G. Instructions for Residents .................................................................. 86
Appendix H. Instructions for Occupants................................................................. 87
Appendix J. Check Sheets/Log Sheets/Certification of Equipment and Systems . 88
Appendix K. Nomenclature / Abbreviations/ Definitions ........................................ 99
1
1 Introduction
The purpose of this guide is to assist the person having control of premises in
discharging their statutory fire safety responsibilities under section 18(2) of the Fire
Services Acts 1981 and 2003. Section 18(2) places a duty on persons having control
over a wide range of premises types, but excluding premises consisting of a dwelling
house occupied as a single dwelling.
Additionally in the case of places of assembly, The Fire Safety in Places of Assembly
(Ease of Escape), Regulations, 1985 apply (see Section 5.4.1 below).
While the guidance in this document is relevant to the management of fire safety in
all premises (including buildings containing flats/apartments) covered by section 18,
additional specific guidance regarding buildings containing flats/apartments is
provided in Section 7.0 of this document.
Fire precautions are generally classified into three broad areas:
Fire Safety Management:
Passive Fire Protection:
Active Fire Protection:
This guide is intended to assist every person having control over premises in the
practical understanding and effective management of the fire safety requirements,
and in discharging their statutory responsibilities for fire safety in premises. The text
of the relevant section of the legislation is given in Section 4.0.
In general, the person having control is required to guard against the outbreak of fire
on the premises and to ensure as far as reasonably practicable the safety of persons
on the premises in the event of an outbreak of fire. If a fire emergency occurs in a
premises, it is imperative to respond effectively by evacuating the premises, and
calling the fire service.
The person having control is legally required to make provision for fire safety on the
premises; this includes providing a premises that is safe including structural fire
precautions, such as fire resistance of elements of structure, protection of escape
routes and compartmentation appropriate to the building.
2
Additionally, management of fire safety should ensure that all necessary reasonable
fire safety measures and procedures are in place. This may include ensuring all
fire safety systems are regularly checked, inspected and maintained (see section
6.0), ensuring suitable provision of fire safety within the premises and carrying out
repair works, as and when necessary. If the person having control requires advice
with respect to such matters, they should engage competent persons.
This guide sets out general management practices for fire safety which should be
applied, having regard to the individual circumstances of each premises
On-going, routine and planned testing and servicing of fire safety equipment and
systems is an essential part of the process to ensure fire safety in buildings or
premises.
Additionally, section 18(3) places a duty on every person on such premises,
including buildings containing flat/apartments, to conduct themselves in such a way
as to "ensure that as far as is reasonably practicable any person on the premises
is not exposed to danger from fire as a consequence of any act or omission of his".
In this regard, it would be useful to inform the relevant persons of these duties.
Where any works are proposed in buildings they should be carried out by competent
persons, and where necessary, designed, specified, supervised and certified by a
competent professional.
Where necessary, a full fire safety assessment of the provisions for fire safety in a
premises may be undertaken. Guidance on fire safety assessment, and suitable
qualifications for those engaged by the person having control to carry out such an
assessment, is available in the “Code of Practice for fire Safety Assessment of
Premises and Buildings” published by Department of Housing Local Government
and Heritage. (See Other Publications, below.)
Users of this guide are advised that the interpretation and application of the more
complex technical information contained in this document should be entrusted to
competent persons.
It is recognised that, as there are many types of premises and as there are
differences in the types of buildings, there may be a need for flexibility in the
implementation of this guide in particular cases.
3
Guides and codes of practice, relevant for a range of existing buildings, have been
issued by the Department of Housing, Local Government and Heritage these
documents provide guidance specific to the type of premises concerned, on
compliance with Section 18(2) and, in the case of places of assembly, compliance
with the Fire Safety in Places of Assembly (Ease of Escape), Regulations 1985.
They are available at the Department’s website (www.gov.ie/housing), and are listed
here in Other Publications, below.
A local fire authority may give advice in relation to fire safety to the owner or occupier
of any premises or to any person having control over any premises.
1.1 Special Hazards
This guide provides guidance in respect of the majority of fire safety issues expected
to arise in buildings generally. Additional considerations may be required where
flammable, explosive, or potentially explosive materials are stored or deposited in
buildings.
Reference may be made to other published guidance in relation to these premises
types, for example: “Guidance document on fire safety in stores for explosives”
published by Department of Housing Local Government and Heritage (2008), see
other publications below.
Some premises may contain specific hazards such as:
magazines or explosive stores
petroleum stores
oil jetties
In addition to the Fire Services Acts 1981 and 2003, other legislation may apply at
these premises:
Dangerous Substances Act, 1972
Explosives Act, 1875
Safety Health and Welfare at Work Act, 200
4
2 Interpretation
This guide is an aid to, and not a substitute for, professional judgement and/or
common sense, and accordingly:
It should be noted that this guide does not purport to be a statement or legal
interpretation of the relevant sections of the Acts or of any of the Regulations
made under the Acts. It is not intended as a substitute for professional legal
advice.
This guide is not a legal interpretation of, or substitution for, the legislation and
is non-exhaustive.
The recommendations in this guide are advisory only and are not statutory
requirements. Compliance with them does not confer immunity from statutory
obligations nor exempt a person from the need to ensure that any relevant
statutory requirements are complied with.
5
3 Persons Having Control (PHC)
The person having control may be an individual person, a number of persons or an
organisation such as those indicated in Figure.1. In other circumstances, some or
all these parties could share the responsibility of the person having control,
depending on tenancy agreements and/or other arrangements. The level of
responsibility may depend on the amount of control a person or an organisation
(such as an owners’ management company, approved housing body, real estate
investment trust or property services company) exercises over the premises and its
operation.
Figure 1 Diagram to illustrate the parties that may hold or share in section 18(2)
responsibilities
It is the responsibility of the person having control to ensure that all necessary and
appropriate arrangements are in place to deal with the safety of persons on the
premises in the event of fire. In small premises, this role might only be a part of the
Person Having Control
Owners
Management
Company
Landlord
Leasee
Housing
Authority
Tenant of
Premises
Owner
Property
Services
Company
Facilities
Manager
Occupier
Approved
Housing
Body
Person
Hiring
Premises
Caretaker
Estates
Manager
6
person’s job/tasks. This responsibility may be shared amongst a number of parties.
(see Figure 1)
The level of responsibility placed on a person may, to an extent, depend on the level
of control they exercises over the premises. For example, the owner of premises
might normally be expected to ensure that the structural fire safety of the premises is
adequate, while, in addition to the owner, a person hiring the premises for a period,
might normally be expected ensure fire safety in the operation of the premises for
example: to prevent overcrowding, to check that the fire exits are unlocked and clear,
and that any decorations introduced on a temporary basis do not present a fire
hazard.
Where section 18(2) responsibilities are shared between a number of parties for
example, between landlord and tenant(s), a property manager, or between occupiers
of different parts of a building allocation of responsibility for management of fire
safety (including maintenance of the premises, maintenance of active fire safety
systems such as fire detection and alarm systems, emergency lighting systems,
evacuation procedures, etc.) should be clear to all parties involved. The lease the
contract between the parties should clearly identify where responsibility lies.
The person having control may delegate specific fire safety duties to members of
staff or members of an organisation; however, the person having control should
retain overall responsibility for ensuring delegated tasks are carried out.
3.1 Competent Persons
For the majority of premises owners /operators, fulfilling their section 18(2)
responsibilities may not require specialist knowledge or expertise. There are general
daily routines, such as checking the fire alarm panels and ensuring that escape
routes are available for egress, and doors on escape routes are in working order,
which can be undertaken by persons who have received a suitable level of training
see Section 8, Table 2 Maintenance Programme Schedule, below.
For the planned periodic maintenance of fire protection systems, such as fire
detection and alarm systems, emergency lighting systems, etc., or for repairs to fire
protection systems, the person having control should engage competent persons.
7
Where the person having control is considering any building works that may impact
fire safety, or requires advice on the suite of technical provisions for fire safety in a
premises, they should engage persons with appropriate qualifications and experience
who are in one of the following categories to design, specify and supervise any
works:
Registered Architects that are on the register maintained by the RIAI under
Part 3 of the Building Control Act 2007,
Building Surveyors that are on the register maintained by the SCSI under Part
5 of the Building Control Act 2007,
Chartered Engineers on the register maintained by Engineers Ireland
under section 7 of the Institution of Civil Engineers of Ireland
(Charter Amendment) Act 1969, or,
Members of the Institution of Fire Engineers who hold the title
Chartered Engineer.
A noted above, the local fire authority may give advice on fire safety to the
owner or occupier of any premises or to any person having control over any
premises.
8
4 Requirements under the Fire Services Acts 1981
and 2003
The person having control is legally required to provide a property / premises that is
safe and all necessary reasonable fire safety measures and procedures are in place.
This may mean oversight and implementation of the fire safety features, measures
and procedures within the premises, and carrying out remedial works and
maintenance as and when necessary. There are different duties which apply to two
different sets of persons -
(a) Owners, occupiers, etc.
(b) Visitors to premises, customers, contractors, residents etc.
9
4.1 Section 18(1)
An extract from the Fire Services Acts 1981 and 203 is as follows
Section 18 - General obligations with regard to fire safety Section 18(1)
“This section applies to premises or any part thereof put to any of the following uses
(a) Use as, or for any purpose involving the provision of, sleeping
accommodation, excluding premises consisting of a dwelling house occupied
as a single dwelling;
(b) Use as, or as part of, an institution providing treatment or care:
(c) Use for purposes of entertainment, recreation or instruction or for the purpose
of any club, society or association:
(d) Use for the purpose of teaching, training or research;
(e) Use for any purpose involving access to the premises by members of the
public, whether on payment or otherwise,
Amendments made in 2003 brought the following premises into the scope of the
Acts:
i. premises used as a factory within the meaning of the Safety in Industry Acts
1955 and 1980:
ii. premises used as a store and subject to licencing under regulations made
under the Dangerous Substances Act 1972:
iii. a magazine, store or registered premises within the meaning of the
Explosives Act 1875:
iv. an oil jetty within the meaning of regulations under the Dangerous
Substances Act,1972:
v. any workplace.
10
Section 18(2)
“It shall be the duty of every person having control over premises to which this
section applies to
a) take all reasonable measures to guard against the outbreak of fire on such
premises;
b) provide reasonable fire safety measures for such premises and prepare and
provide appropriate fire safety procedures for ensuring the safety of persons
on such premises;
c) ensure that the fire safety measures and procedures referred to in
paragraph (b) are applied at all times; and
d) ensure, as far as is reasonably practicable, the safety of persons on the
premises in the event of an outbreak of fire whether such outbreak has
occurred or not.
4.2 Section 18(2)
Section 18(2) sets out duties which are which are placed on the person(s) having
control of premises to which Section 18 applies.
Table 1 below illustrates an example of measures and actions that may apply in the
case of a building with a licenced premises with flat above, to comply with the
requirements of section 18(2) of the Fire Services Acts. (This is illustrative only, and
should not be regarded as covering the complete range of measures and actions that
may be required in every premises.)
11
12
Table 1
Section 18(2)
2) It shall be the duty of every person
having control over premises to which
this section applies to
(a) Take all reasonable measures to
guard against the outbreak of fire
on such premises,
(b) Provide reasonable fire safety
measures for such premises and
prepare and provide appropriate
fire safety procedures for
ensuring the safety of persons on
such premises,
(c) Ensure that the fire safety
measures and procedures
referred to in paragraph (b) are
applied at all times, and
(d) Ensure, as far as is reasonably
practicable, the safety of persons
on the premises in the event of an
outbreak of fire whether such
outbreak has occurred or not.
Maintain a Fire safety register
o Identify person(s) having control over
premises, and allocate duties and
responsibilities
o schedule and record routine fire safety
visual checks/inspections, training, fire
drills, servicing and systems maintenance
Put in place a fire safety programme to
include the following:
o Carry out fire safety duties and
responsibilities of the person having
control or assign some or all to
responsible staff members
o Periodic inspection of electrical installation
o Periodic inspection of gas and oil
installations
o Control of other sources of ignition such
as matches, candles, smokers’ materials,
overloaded electrics, open fires
o Regular removal of waste to avoid build-
up of combustible materials
o Control of readily combustible materials,
such as decorations or displays
o Safe storage of flammable liquids in
limited amounts and in suitable containers
o Closing procedure: making premises safe,
Isolating and unplugging electrical
equipment
Provide a property / premises that is safe
o Robust building structure and fabric
o Fire resisting construction to separate
commercial premises from living
accommodation, and contain a fire event
o Provision for early warning - fire detection
and alarm system (typically, category L3X
13
’X’ for interlinking between commercial
premises and living accommodation)
o Emergency lighting, to facilitate escape
o Sufficient number of suitable escape
routes
o Maintenance and repair as required
Provide fire extinguishing equipment
Provide training for staff at recruitment, and
at regular periods housekeeping, control
of ignition sources, waste removal,
procedure on discovering a fire or hearing
fire alarm, ensuring people evacuate the
building promptly and safety, calling the fire
service, safe use of fire extinguishers,
assisting the fire service on arrival, visual
inspection of fire alarm panel, emergency
lighting, fire doors, opening up of premises
procedure (see 5.3.2 below)
Notices for procedure in the event of fire or
alarm:
o for commercial premises, and
o for flat above
Signs for escape routes
Provide fire safety information to occupants
of living accommodation
Routine visual check of fire alarm panel,
emergency lighting luminaires,fire
extinguishers, signage visibility
Routine check on operation of fire doors,
escape routes, doors on escape routes, exit
doors
Regular maintenance (by competent
persons) of fire alarm system, emergency
lighting, fire doors, fire extinguishers (see
Section 8 Table 2 Routine Maintenance
below)
14
Section 18(3)
“It shall be the duty of every person, being on premises to which this
section applies, to conduct himself in such a way as to ensure that as
far as is reasonably practicable any person on the premises is not
exposed to danger from fire as a consequence of any act or omission of
his
4.3 Section 18(3)
The section 18(3) of the Fire Services Acts 1981 and 2003 also places a duty of care
on every person being on the on premises. Any person on any premises covered by
the Act they could be a tenant, living or working there, just visiting, attending a
show or meeting, etc. is under an obligation to conduct themselves properly.
There are two sides to this obligation, referred to in the legislation as an act or an
omission. To do anything which would expose anyone to danger from fire (an act)
may be a breach of Section 18(3). In addition, failure to do something which would
prevent people from being exposed to danger from fire (an omission) may be a
breach of Section 18(3).
4.4 Inspection and Enforcement
While fire safety on premises is the responsibility of the person having control, fire
services have powers of inspection, and may take enforcement action where
necessary to deal with unsatisfactory provision for fire safety on premises.
Enforcement powers include:
provision of advice in relation to fire safety
service of notice requiring steps to be taken in relation to fire safety on
premises,
service of notice requiring closure of premises,
seeking an order of the High Court, prohibiting or restricting use of premises,
or part thereof.
The Fire Services Acts also provide for penalties for contravention of Part III of the
Acts, of regulations made under the Acts, or of notices to which the Acts apply.
15
Penalties on conviction can include fines and/or imprisonment potentially up to 2
years imprisonment, fine up to €130,000, or both.
4.5 Section 20(5)
The aforementioned requirements of Section 18(1), (2) and (3) of the Fire Services
Acts 1981 and 2003 address requirements with regard of ensuring the safety of
occupants within buildings. Section 20(5) additionally, places a duty of care on the
person having control of buildings where flammable, explosive or potentially
explosive substance is used, stored or deposited adjacent to buildings.
Section 20(5)
Where a fire authority is of the opinion that a flammable, explosive or potentially
explosive substance is used, stored or deposited adjacent to buildings in such a
manner as to represent a serious danger to life, the authority may serve a fire safety
notice on the owner or occupier of the land on which the substance is used, stored or
deposited requiring the taking of specified measures to reduce the danger to a
reasonable level.
16
5 Main Duties for Persons having Control
Every person having control, as outlined above, has a statutory responsibility in
relation to fire safety. This section provides standardised procedures for the
development and implementation of a fire safety programme which should be an
integral part of the day-to-day management and operation of premises.
There should be clear understanding on the subject of fire safety measures and
emergency procedures, to ensure that no element of fire safety is neglected, and no
element is unreasonably duplicated, where this could cause confusion in an
emergency.
5.1 Fire Safety Programme
A fire safety programme incorporating arrangements for the following should be
prepared for each individual premises:
- prevention of outbreaks of fire, through the establishment of day-
to-day fire prevention practices;
- instruction and training of staff on all matters relating to fire safety;
- emergency fire procedures and evacuation drills;
- provision of fire safety notices/instructions to people on the premises;
- routine check of fire alarm panels, emergency lighting, portable fire
extinguishers, etc.
- routine check of operation of fire doors, doors on escape routes,
exit doors
- periodic maintenance of fire protection equipment: fire detection
and alarm systems, emergency lighting, fire doors, etc.
- maintenance of the building, and its fittings and services;
- maintenance of escape routes;
- liaison with the fire authority and assisting the fire service ; and
17
- keeping of fire safety records (Fire Safety Register)
A fire safety programme will be effective only if it is implemented in total, and
monitored on a day-to-day basis by the persons having control. Most of the areas
covered in this section are matters of good housekeeping and can contribute to the
maintenance of fire safety standards in a premises.
5.2 Fire Prevention
Fire prevention measures are a key element in the fire safety management of
premises. This involves the identification and elimination of potential fire hazards,
both inside and outside the premises/building, and the establishment of good
housekeeping practices, periodic inspections, and the diligent application of safety
rules. The following fire prevention measures are recommended for adoption in the
day-to-day running of the premises.
5.2.1 Rubbish and Waste
Arrangements should be made for collection and removal of waste at regular
intervals. Pending removal, rubbish and waste should be stored in suitable
containers at a designated location, away from sources of ignition. Staff should be
made aware of the importance of keeping all areas of the premises clean and tidy.
Rubbish and waste should never be allowed to accumulate in stairways or escape
routes.
5.2.2 Smoking
Smoking and careless disposal of smokers' materials is a common potential cause of
accidental fires. Where permitted, smoking should be restricted to approved areas. In
smoking areas, suitable ashtrays should be provided. Ashtrays should be emptied
frequently into metal bins, with any smouldering material being extinguished
beforehand.
5.2.3 Storage of Gas Cylinders/Cartridges
Where pressurised gas cylinders are stored in buildings, storage should be in
accordance with relevant standards. Cylinders and cartridges containing liquefied
petroleum gas should be stored in accordance with Irish Standard I.S. 3213:2020,
Code of Practice for the storage of Liquid Petroleum Gas Cylinders and cartridges.
18
Other gas cylinders should be stored in accordance with the British Compressed
Gases Association: CP44. The storage of gas cylinders. Revision1:2022.
5.2.4 Storage of flammable, explosive or potentially explosive
substance Gas Cylinders/Cartridges
Flammable, explosive or potentially explosive substance should not be used, stored
or deposited adjacent to buildings in such a manner as to represent a serious danger
to life.
5.2.5 Electrical Installations and Appliances
(a) Installations
Inspection and testing of the electrical installation should be carried out by
a competent registered electrical contractor in accordance with Irish
Standard 10101. The Health and Safety Authority has issued a Guidance
Note giving practical advice which can assist every person having control
to put in place a suitable regime for periodic inspection and testing of
electrical installations. (See other publications, below.)
(b) Appliances
Staff should be trained to use electrical equipment correctly and safely,
and to report defective electrical equipment. Defective equipment should
not be used; repairs as appropriate should be carried out only by
competent persons. Equipment should be switched off when not in use.
5.2.6 Heating and Ventilation Systems
All ventilation and heating systems in buildings including air conditioning systems
should be maintained in accordance with the manufacturer’s recommendation. Any
filters, vents, access points, fans, etc. should be regularly cleaned of oil, grease and
dust.
19
5.2.7 Kitchens
Good housekeeping practices are essential for fire safety in kitchens. Cookers,
extract fans, extraction hoods, filters, ducts and ancillary equipment should be
regularly cleaned of oil, grease and dust. Equipment should be serviced regularly.
Precautions should be observed in kitchens for example:
- do not leave cooking operations unattended;
- take care not to overheat fats/oils;
- do not over-fill cooking pans; and
- do not leave combustible materials (for example, towels, etc.) over stoves.
Staff should also be familiar with the location, and receive training in the safe and
correct use, of available first aid fire-fighting equipment and procedures for
example, portable fire extinguishers, fire blankets and any fixed fire suppression
systems and use of emergency shut-off switches.
5.2.8 Laundries
Rooms used as laundries should be separate rooms. Such rooms may pose
particular fire hazards as detailed below.
(a) spontaneous combustion of compacted fabrics which have been tumble
dried. Tumble dryers should have automatic cooling at the end of the drying
cycle. Fabrics should not be over-dried, and tumble dryers should be
unloaded immediately after use and left empty. Tumble-dried fabrics should
be loosened to dissipate heat on being taken from the machine.
(b) Fluff or lint, which is readily flammable, can accumulate in laundries. Such
materials should be removed on a regular basis especially from hot areas,
such as electric motors, tumble dryers, and other hidden locations. Filters
should be regularly inspected and cleaned.
(c) Ironing equipment should be switched off when not in use.
(d) Solvents which are highly flammable are sometimes used for spot cleaning
in laundries. Only small quantities needed for immediate use should be kept
in the laundry. The main bulk of this type of liquid and general cleaning
solvents should be stored in a suitable lockable metal cabinet. Containers
20
for solvents should be kept closed, to prevent vapours leaking.
(e) Smoking should be prohibited in laundries, and signs to this effect should
be displayed.
5.2.9 Flammable Liquids
Where flammable liquids are used in buildings, quantities should be limited to those
needed for immediate use. If larger quantities are stored, they should be in a suitable
lockable metal cabinet. Containers for flammable liquids should be kept closed, to
prevent vapours leaking.
5.2.10 Hot Work
Adequate fire precautions should be taken when any hot work such as soldering,
welding, etc. is undertaken, and the work should be carefully supervised. The
activities carried out by outside contractors may introduce additional fire risks. They
may not be as familiar with the premises as those normally present.
The person having control should ensure that all necessary precautions against fire
are taken including engaging only competent contractors.
The person having control should ensure that escape routes are not blocked or
obstructed. Access by the occupants to areas of hot work should be restricted. Where
work involves removing or switching off fire protection facilities, alternative
arrangements to maintain safety levels should be made.
Hazardous equipment and materials should be removed from the building at the end
of each working day, and a final check should be made to ensure that no fire danger
remains after work finishes.
5.3 Staff Training
For a fire safety programme to be effective, staff should be familiar with the parts of
the fire safety programme in which they have a role. Instruction and training on the
relevant areas should be given to all staff, including part-time and temporary staff. A
record of the training undertaken by the staff should be kept in the Fire Safety
Register (see Section 5.7).
21
Staff should receive training and instruction in relation to the following, where
relevant to their duties and roles:
- the fire prevention measures indicated in Section 5.2 above;
- the action to be taken on hearing the fire alarm;
- the action to be taken on discovering a fire;
- the evacuation procedure for the premises;
- the layout of the building, including escape routes;
- the role of fire doors in controlling fire and smoke spread, and protecting escape
routes;
- the location of manual fire alarm call points and fire-fighting equipment;
- the location of the main fire alarm control and indicating panel and any
associated alarm panels and their operation;
- the procedure for calling the fire service;
- arrangements for assisting the fire service;
- fire control techniques, including the safe use of first aid fire-fighting equipment;
- the operation of building services (for example, shutting down air conditioning
systems) to minimise fire and smoke spread;
- action to be taken where fault, damage or ineffective operation of fire protection
systems (for example, fire detection and alarm systems, emergency lighting) or
elements (for example, fire resisting doors) is noticed
5.3.1 Fire Emergency Plan
If a fire emergency occurs in a premises, it is imperative to respond effectively by
evacuating the premises, and calling the fire service. Accordingly, a predetermined
plan should be put in place, outlining the procedures to be adopted:
- a procedure for raising the alarm;
- an evacuation procedure for the occupants, including persons with
disabilities
- a procedure for calling the fire service;
- a procedure for reporting to pre-determined assembly point(s) and informing
designated person(s) of the situation;
- a procedure for accounting for each person on the premises;
- a procedure for assisting the fire service on their arrival.
22
5.3.2 Evacuation Drills
To assess the effectiveness of the predetermined plan and preparatory training
given, drills which simulate fire and emergency situations should be carried out on a
regular basis. These drills can generally be organised for times which cause
minimum disruption to the operation of the premises, but all staff must be involved.
The objectives of drills are generally;
- to familiarise persons in control with their assigned roles;
- to test the availability and effectiveness of staff training;
- to test arrangements for an emergency; and
- to identify shortcomings in the emergency procedures.
Each drill should be reviewed afterwards, and procedures revised if necessary. All
drills should be recorded in the Fire Safety Register.
5.3.3 Fire Safety Instructions for Occupants
In addition to instructions for staff, written instructions on the action to be taken by
building occupants on the discovery of a fire or on hearing the fire alarm should be
displayed in prominent positions throughout the building. Instructions should be
accompanied by a simple floor plan, showing schematically the location of all storey
exits. Particular attention should be drawn to the general advice that lifts should not
be used in the event of fire. An example of the notice required, together with the fire
safety instructions, is given in Appendix H.
5.4 Escape Routes
In the event of a fire or other emergency, occupants should be able to evacuate the
premises quickly and safely, by way of routes protected from fire and smoke and free
from obstruction. This can only be achieved if escape routes are unobstructed, if fire
resisting doors are kept closed, and if exit doors are readily openable at all times
while the premises is occupied. All escape routes should be checked on a daily
basis. If any obstruction is noticed in the areas of escape, then it should be removed
immediately and any necessary steps taken to prevent a recurrence.
23
Daily checks of escape routes should be carried out in accordance with Section 8
Table 2 Maintenance Programme Schedule, below.
All fire safety signs, notices and instructions which are provided for the building
users, staff and the fire service should be prominently displayed and be fully and
clearly visible at all times. Damaged items should be repaired or replaced.
5.4.1 Escape routes in Places of Assembly
Premises which are used as a place of assembly may accommodate large
numbers of occupants. A "place of assembly" means a building or any part of
a building put to any of the following uses:
amusement arcade
art gallery
assembly hall
bingo hall
concert hall
conference hall
cinema
dance hall
ecclesiastical building
exhibition hall
funfair building
grandstand
gymnasium
indoor bowling ally
indoor games court
library to which the public are admitted
museum
non-residential collage or school
non-residential club
premises licenced for the sale of intoxicating liquor other than an off-
licence
radio or television studio to which the public are admitted
24
restaurant, café, canteen
riding school
skating rink
sports pavilion
stadium
swimming baths(including any swimming pool, changing rooms, or similar
facilities)
tent or marquee to which the public are admitted
theatre
The Fire Safety in Places of Assembly (Ease of Escape), Regulations, 1985 apply to
these premises (S.I. No. 249/1985) and set out some additional fire safety
requirements relating to escape routes and ensuring that they can be readily used at
all times.
25
5.4.2 Overcrowding
In all premises, the person having control should guard against overcrowding which
could inhibit escape of the occupants. There may be potential for overcrowding in
any building.
In the case of premises licenced under the Public Dance Halls Act, 1935 and 2003,
the maximum number of persons permitted on the premises/licenced area may be
set out as part of the licence conditions
Regulation 4
“every person having control over a place of assembly shall take the following
precautions that is to say, he shall ensure that, while the place is in actual use as a
place of assembly
e) Subject to paragraph (ii), all escape routes are kept unobstructed and
immediately available for use;
f) Doors, gates and other like barriers across escape routes are not secured in
such a manner that they cannot easily and immediately opened by persons in
the place of assembly
g) All chains, padlocks and other removable fastenings for securing doors, gates
or other like barriers are removed and kept in a place where they may be
readily inspected by an authorised person for the purpose of section 22 of the
Fire Services act,1981,
h) No hanging or drape is placed across or along an escape route in a manner
which would impede or obstruct escape
26
5.5 Liaison with the Fire Authority and Assisting the Fire
Service
5.5.1 Liaison with the Fire Authority
It may be appropriate to liaise and consult from time to time with the local fire
authority with the following objectives:
- familiarisation of the fire service with the premises;
- to ensure the availability of access and appropriate facilities for the fire
service;
- advice on fire safety matters and fire safety management generally.
5.5.1 Assisting the Fire Service
Access routes to premises, including private access roads should be accessible or
arrangements should be put in place to facilitate fire service access. Obstruction of
private access routes for example, by waste skips or parked vehicles should be
prevented.
Facilities, such as fire hydrants and other fire-fighting water supplies, dry risers, foam
inlets, etc., should be immediately available for use by the fire service.
All firefighting lifts should have a notice displayed adjacent to the lift entrance at fire
service access level indicating the maintenance history of the lift, including the date
of the most recent weekly, monthly and six monthly checks and tests.
Signs should be provided in firefighting shafts as follows:
(a)
A storey identification sign, in each firefighting stairs, at each storey
landing, that identifies the floor by number.
(b)
A storey identification sign, in each firefighting lobby, that identifies
the floor by number.
Where there is more than one firefighting shaft in a building, the storey identification
number should be supplemented by a shaft identification number (e.g. A-1, A-2, etc.,
or similar).
27
5.5.2 Plan of Premises
Plans of the building and site should be made available to the fire service upon their
arrival. Such plans should indicate the following:
- Building layout, including stairways and escape routes;
- fire protection facilities;
- first aid fire-fighting equipment; gas and electricity supply shut-off points;
- storage of gas cylinders and other hazardous materials;
- the fire alarm panel for the automatic fire detection and alarm system
- the control device for any ventilation systems.
- site layout plans
5.6 Fire Safety Register – Record Keeping
5.6.1 Fire Safety Register
A Fire Safety Register should be maintained for all premises where section 18
applies. The maintenance of a Fire Safety Register will assist in meeting the general
obligations, imposed by section 18 of the Fire Services Acts, and is a means of
demonstrating compliance
28
The person having control should retain and make available the Fire Safety register
for the premises. This register should be kept on the premises at all times, be kept
up-to-date, and should be available for inspection by an authorised officer of the fire
authority.
The Fire Safety Register should be a living document with daily, weekly, monthly,
quarterly and annual records of fire safety checks of procedures and the life safety
systems within the premises.
Larger, more complex premises may have correspondingly a more comprehensive
Fire Safety Register and schedule of contents, with other engineering fire safety
systems listed, and records of the appropriate maintenance and certification of those
systems included.
This information in the Fire Safety Register may also be useful in any future
maintenance or renovation. Most active and passive fire safety systems require
periodic maintenance/proactive intervention, and it is necessary for all interventions to
be properly recorded.
The Fire Safety Register should be produced and maintained in a user friendly format
suitable for ongoing use. The following information should be regarded as an indicative
schedule of contents: (Note - this list is non-exhaustive and not in any order of
preference)
Figure 3 Sample Fire Safety Register
29
details of premises (address, owner, management company),
the name of the person in control the owner/occupier/manager, and any
deputies; fire and emergency procedures;
fire duties assigned to staff members;
information regarding:
emergency lighting systems (Installation, Inspection, maintenance, and
works carried out),
fire detection and alarm system (zones, detectors, manual call points,
inspections, false alarms, maintenance, and works carried out),
fire doors (inventory, inspections, maintenance, and works carried out),
sprinkler systems water,
fire suppression systems -gas, foam,
smoke control systems,
fire mains dry/wet fallers dry/wet risers,
static water storage, bulk tanks,
portable fire extinguishers
up-to-date construction drawings and specifications; these may include
drawings prepared as part of an application to the local building control
authority for a fire safety certificate, and any conditions attached to the
certificate
details of instruction and training given to staff on fire safety, and by whom;
details of each fire and evacuation drill, the date thereof, the names of those
taking part, and the type, objective and results of exercises held;
manuals, and where appropriate certificates, produced by specialist
contractors and suppliers which outline operating and maintenance
procedures and schedules for plant and equipment installed as part of the
30
structure;
details of the location and nature of utilities and services, including
emergency and fire-fighting systems;
details of routine checks, planned inspections and maintenance carried out
on fire protection equipment and systems, with comments on the results of
the checks and inspections and actions taken (and by whom) to address
defects;
details of each inspection of the building itself, its fittings and services and
the actions taken to remedy any defects found; and
details of all fire incidents and false alarms that occur and the actions
5.6.2 Additional Information
Additionally, persons having control might find the following document useful in
providing information regarding the structure and fabric of the premises/building.
Certificate of compliance on completion, where applicable
31
6 Fire Safety Maintenance and Testing
The safety and protection of the occupants in the event of a fire will depend greatly
on the reliable functioning of fire protection equipment, such as fire detection and
alarm systems, emergency lighting systems, fire doors, smoke ventilation systems,
fire extinguishing equipment and sprinkler systems. In buildings, a high degree of
reliance may be placed on such active fire precautions, and accordingly, the person
having control should ensure that such equipment is operated and maintained to the
appropriate standards.
All such equipment should be checked by the person having control, or designated
member of staff, and inspected and maintained on a regular basis by a competent
person. Details of checks and inspection procedures for fire protection equipment are
given in Section 8, Table 2 Maintenance Programme Schedule, below. If faults or
deficiencies are discovered, they should be noted and corrective action should be
taken, as well as any appropriate steps to prevent a recurrence. Maintenance should
be arranged with competent companies or persons in accordance with the
appropriate standards.
It is important to maintain the condition of the premises/building over time, including
passive fire protection features. The integrity of walls, doors or floors which are part
of fire compartmentation or the protection of escape routes is an important feature of
passive fire protection. When repairs or alterations are made to building structures, it
should be ensured that fire resisting walls or other passive fire protection systems are
reinstated if damaged. Any alterations, additions, repairs or modifications should to
be carried out only by competent persons.
6.1 Fire Safety Systems: Testing, Inspection and
Maintenance
Planned inspection, maintenance and testing procedures should be established and
used to ensure that all fire protection systems can operate effectively when required.
Faults are a life safety issue not simply a maintenance issue to be dealt with later;
faults should be entered in the fire safety register and corrected promptly.
32
Maintenance should be carried out in accordance with the relevant standards or
manufacturer’s Instructions at the recommended time intervals, and the testing and
inspection of these systems should be carried out by competent persons.
All fire safety installations should be tested individually, but interdependent fire safety
installations should be tested collectively, to demonstrate satisfactory interfacing /
interlinking (cause and effect) for example, operation of automatic opening vents
upon the activation of localised fire detection and alarm system.
A clear understanding of how the fire safety equipment and systems operate
independently and/or collectively is key to the establishment of the planned routine
maintenance programme.
The maintenance requirements for all fire safety equipment and systems should be
sought from the equipment and/or system manufacturers, suppliers, their technical
advisers and/or specialised contractors. The following non exhaustive list details
equipment and systems which require ongoing management and routine
maintenance:
fire detection and alarm system
emergency lighting system
fire doors and doors on escape routes
dry mains, dry risers, wet risers, inlet breechings, landing valves, etc.
fire fighting shafts and lifts
first aid fire fighting equipment, including hose reels (if provided/ required)
smoke control systems (common areas, such as corridors, lobbies and
stairwells)
sprinkler systems
signposting and way-finding measures to assist firefighting
signposting fire hydrants and water supplies
special provisions for example, fire/smoke curtains and shutters, etc.
33
6.2 Fire Detection and Alarm Systems
The majority of buildings will include a fire detection and alarm system installation
(see Figure 4). A fire detection and alarm system can be a simple manual system,
with only manual call points (break glass units). In larger or more complex
buildings a system will typically include automatic detection (smoke or heat
detectors).
The person having control should have a clear understanding and written description
of the extent of the fire detection and alarm system, and any interaction with the active
fire safety systems. In a larger building, the fire detection and alarm system may
consist of number of separate alarm zones. This can allow the fire alarm panel (see
Figure 5) to indicate the location of a fire, in the event of an alarm activation, or a fault
in the system.
Figure 4 Fire Alarm and Detection System
Figure 5 Fire Alarm Panel
34
A zone plan drawing should be displayed on a wall next to the fire alarm panel.
This should indicate the locations of the fire detection and alarm zones in layout
form for all floors throughout the building. Additionally the schedule of
servicing/testing should also be displayed at this location (in accordance with Irish
Standard I.S. 3218)
The Fire Safety Register should contain details of the fire detection and alarm
system. Fire detection and alarm systems should be inspected and maintained in
accordance with the recommendations of the Irish Standard IS 3218.See section
8,Table 2 Maintenance Programme Schedule,below
Section 18(3) of the Fire Services Acts 1981 and 2003 places a duty on each
occupant to ensure that any person on the premises is not exposed to danger from
fire as a consequence of any act or omission on their part. Reasonable access
should be allowed for maintenance of the common alarm system. Section 7
provides additional information for fire detection and alarm systems in buildings
containing flats/apartments.
6.3 Emergency Lighting System
In general, buildings are required to include an emergency lighting system typically
used to illuminate escape routes, common areas, corridors, stairways and service
rooms, etc. Irish Standard I.S. 3217 sets out requirements for installation, testing and
maintenance of emergency lighting systems.
The overall objective of emergency escape lighting is to illuminate escape routes to
assist safe exit from a location in a building in the event of failure of the normal
electrical supply. An emergency lighting fitting (see Figure 6) automatically
illuminates when the power fails, assisting occupants to make their way to an exit.
Emergency lighting systems should be inspected and maintained in accordance with
the recommendations of Irish Standard I.S. 3217. See Section 8, Table 2
Maintenance Programme Schedule, below.
35
Figure 6 Emergency Light Fitting
36
6.4 Fire Doors
Fire doors have two important functions in a fire:
to maintain the fire resistance of compartmentation in buildings
to protect escape routes by keeping them free of smoke and fire, to enable
occupants to evacuate to a place of safety
A reference to a fire door includes the door leaf(s), frame, hardware, including seals
and automatic door closers (See Figure 7). Every fire door is required to act as a
barrier to the passage of smoke and/or fire.
Fire doors may be rated differently, depending on their performance in standard fire
resistance tests, doors commonly found in buildings can offer various degrees of fire
rating eg: 30,60, 90 minutes, where required.
Fire doors are typically fitted with intumescent seals around the door or frame. These
seals reduce the spread of smoke between the door and frame. The seal swells
when exposed to high temperatures, and seals the gaps between door and frame.
Figure 7 Fire Door Components
37
Some fire doors may additionally be fitted with a cold smoke seal (see Figure 7).
Intumescent and cold smoke seals should not be removed or painted over.
Fire doors should be identified by a label affixed to the top edge of the door or
colour-coded plugs inserted into the door to indicate their performance in a fire
resistance test. (See Fire Door Labels A Guide | BWF Fire Door Alliance) They
should also have a permanent sign reading “fire door keep shut” fixed on both faces
see Figure 8 (a). (Entrance doors to flats, and internal doors in flats, and bedroom
doors in some other residential buildings are exempted from this requirement).
Identification marks should not be removed or painted over.
The protection provided by a fire door is demonstrated in Figure 9 where extensive
fire damage has occurred in a car park. This an example of how a fire door in the
closed position prevented fire spreading out of the car park to other parts of the
building, with only minor smoke damage occurring beyond the car park
Figure 8(a) Fire Door Sign
Figure 8(b) Overhead Self Closing Device
38
In order that a fire door be effective, it is essential that it returns to the closed
position and forms a barrier to smoke and hot gases, this closing action is
achieved by the automatic door closing mechanism.
It’s essential that fire doors are not rendered ineffective by being held open by
wedges or other objects. Any other arrangement should be considered only upon the
advice of a competent professional.
Staff moving about buildings on a daily basis who note damage or ineffective
operation of a fire door should bring it to the attention of the relevant person, and it
should be noted in the Fire Safety Register and remedial action taken. Particular
attention should be paid to fire doors where people movement is higher, as these are
likely to be more susceptible to wear.
All fire doors should be inspected and maintained in accordance with the
recommendations in Table 2 Programme Maintenance Schedule, below. Mechanical
items such as hinges, locks, latches, door closers, (see Figure 8 (b)) floor springs
etc. are likely to wear over time; it is important that these mechanisms are checked,
inspected and maintained.
Figure 9 Fire Door
Performance
39
Any slight alteration to the door or its surrounds can affect the performance of the fire
door. Any inspection or maintenance of the fire doors or any alterations or work on a
fire door, should be carried out only by a competent person.
Where it is necessary to replace worn hardware on a fire door, the essential items
should be replaced with products to the same specification as that outlined in the test
certification supplied by the door manufacturer.
Where any alterations are proposed to fire doors, they should be carried out by
competent persons, and where necessary, designed, specified, supervised and
certified by a competent professional.
6.5 Fire Mains: Risers/Fallers
A fire main can be a fixed water supply pipe (riser or faller) installed in building for
firefighting purposes, or can be a ring main which circuits a building to serve fire
hydrants, fire mains or other firefighting apparatus.
Usually, only the larger, complex or restricted developments include wet or dry
riser/faller installations. Risers are fixed pipes provided to facilitate the supply of
water above the inlet level, while fallers facilitate water supply below the inlet level.
Figure 10 Rising Main
40
These may be installed in tall or deep or otherwise complex/inaccessible buildings to
eliminate the need for fire-fighting personnel to run hoses up through the building to
carry out fire-fighting operations (see Figure 10). In the case of wet risers (usually
only taller or complex/inaccessible developments) a detailed maintenance program
is necessary and should be carried out by competent persons in accordance with
Section 8, Table 2 Programme Maintenance Schedule, below.
In the case of dry risers/fallers a certain amount of maintenance is required, to
ensure that the landing valves have appropriate blank caps secured by a chain or
similar, and to deal with any damage that may occur as a result of interference.
Figure 11(a) shows examples of a typical inlet breech, and Figure 11(b) a landing
valve. Dry riser/faller systems should be checked, inspected and maintained in
accordance with the recommendations in Section 8, Table 2 Programme
Maintenance Schedule, below.
6.6 Firefighting Shafts and Lifts
This is a provision that is normally only associated with taller or relatively
inaccessible or complex buildings, and includes a series of features collectively
referred to as a firefighting shaft, which forms a protected area for initiating fire-
fighting operations. It normally includes a protected stairway, firefighting lift and
Figure 11(b) Landing valve in
stairway at upper levels
Figure 11(a) Inlet Breeching at exterior
of building
41
protected approach lobby enclosed in fire resisting construction (see Figure 12(a)),
along with a dry or wet riser and specific ventilation provisions.
Ventilation can be achieved by means of an openable window, naturally or
mechanically ventilated smoke shaft. A firefighting lift, unlike a normal lift, is
designed to operate for as long as is practicable when there is a fire in the building.
Additional lift control system features (see Figure 12(b)) are required above those
which would be incorporated on a normal lift. Firefighting lifts should be inspected
and maintained in accordance with the recommendations in Section 8, Table 2
Programme Maintenance Schedule, below.
6.7 First Aid Firefighting Equipment, including Hose Reels
First-aid firefighting equipment can make a valuable contribution to containing and
extinguishing fire, when operated by a trained user.
Where provided, portable fire extinguishers (Figure 13(b)) should be suitable for the
class of fire likely to occur. Portable fire extinguishers should conform with European
Standard EN 3, and be installed, inspected and maintained in accordance with lrish
Standard I.S. 291; see recommendations in Table 2 Programme Maintenance
Schedule, below. Where provided, fire hose reel installations (Figure 13(a)) should
be inspected and maintained in accordance with the recommendations in Section 8,
Figure 12(b) Firefighting Lift
Control Features
Figure 12(a) Firefighting Shaft
42
Table 2 Programme Maintenance Schedule, below. Portable fire extinguishers
should be in a fixed, permanent location, such as a stand, or wall mounted, and
generally located on exit routes near exit doors and for specific hazards in
accordance with lrish Standard I.S. 291.
Any extinguisher used in a fire, or otherwise discharged, should be recharged
immediately. Damaged extinguishers or hose reels should be repaired or replaced.
Figure 13(b) Portable Fire Extinguishers
Figure 13(a) Fire Hose Reel
43
6.8 Smoke Control Systems
Smoke Control Systems play an important role in protecting escape routes in many
buildings in the event of fire. The objectives are:
to keep staircases relatively clear of smoke
to keep lobby or corridor relatively clear of smoke
to facilitate firefighting operations
The person having control should be aware of the type of smoke control system in
place and how this is intended to control the spread of smoke in the event of fire.
The person having control may need to seek advice from a competent person or
professional to ascertain how it will function.
Some additional information relevant to smoke control in buildings containing
flats/apartments in given in Section 7.4.
Smoke control systems should be inspected and maintained in accordance with the
recommendations in Section 8, Table 2 Programme Maintenance Schedule, below.
6.8.1 Stairway Smoke Control
For stairways this normally will take one of 3 forms;
1. The provision of manually openable vents (OVs) (in many cases windows on
landings in stairways may fulfil this function) at every level in the stairway
including at high level at the top of the stairway enclosure, or,
2. The provision of a high level automatic opening vent (AOV) at the top of the
stairway (Figure 14(a)), that is opened on activation of smoke detectors in the
stairway enclosure, and is additionally manually openable by fire service
switch at the entrance level (normally at ground floor level) or,
3. The third method of provision namely pressurisation systems which are
less common, and use fans to maintain a positive pressure in the escape
stairway, and thus prevent smoke from entering in the event of a fire
44
6.8.2 Smoke Control in Larger more Complex Buildings
In larger more Complex buildings such as shopping centres and buildings containing
atria, natural, automatic or mechanical smoke extraction systems can also be
employed using roof vents or smoke ventilation shafts.
6.8.3 Smoke Clearance Systems in Enclosed Car Parks
Ventilation of enclosed carparks are employed to limit concentrations of carbon
monoxide (CO) and other vehicle emissions in the day-to-day use of car parks, and
to remove smoke and heat in the event of a fire. The same equipment/system is
often used to satisfy both requirements. The following types of ventilation systems
may be employed for a covered car park area or level(s).
natural ventilation (permanent openings to the exterior) (see Figure 15)
ducted mechanical ventilation systems.
Figure 14(b) Roof mounted Automatic
opening vent
Figure 14(a) AOV in stairway
45
mechanical ventilation systems(see Figure 16)
Louvres, dampers, and powered smoke extraction fans are also often integrated into
the mechanical system
Any ventilation system, unless permanently open (as in Figure 15), is dependent
upon suitable power supplies and controls for correct operation. Ventilation systems
Figure 15 Car Park permanent ventilation openings to the external air
Figure 16 Car Park impulse Ventilation Fan
46
interact with other building services and fire protection systems in normal operation,
whether by design or as a by-product of operation. Figure 16 shows impulse (or jet)
fans used to clear smoke from an enclosed or underground car park. Ventilation
systems should be inspected and maintained in accordance with the
recommendations in Section 8, Table 2 Programme Maintenance Schedule, below
47
6.9 Sprinkler Systems
Sprinkler installations, where provided, (Figure 17(a)(b)) may comprise a single
system throughout the building, or, in buildings containing flats/apartments, may
comprise a discrete domestic sprinkler system in each individual flat /apartment.
Sprinkler systems should be inspected and maintained in accordance with the
recommendations in Section 8, Table 2 Programme Maintenance Schedule, below
6.10 Doors on Escape routes, Final Exit Doors
All doors on escape routes should be readily openable. The time taken to negotiate a
closed door can be critical in an escape situation. Doors on escape routes (both
within and from the building) should be readily openable if undue delay is to be
avoided.
The operation of door fastenings and emergency and panic escape devices (Figure
18), where fitted, should be checked for ease of operation and opening of the door.
(see Section 8, Table 2 Programme Maintenance Schedule, below)
Figure 17(b) Sprinkler Head
Figure 17(a) Concealed Sprinkler Head
48
Particular attention should be paid to external doors which are not regularly used, as
weather conditions can affect the door and frame relationship, and therefore the
ease of operation of escape devices.
Where additional security is required on final exit doors when the premises is not in
use, hardware which is fully removable may be used. Such hardware must always
be removed when the building is occupied.
6.11 Maintenance of Private Fire Hydrants and Water
Supplies
Normally, firefighting operations rely on the provision of appropriate water supply,
usually in the form of fire hydrants, and sometimes as static water supplies, such as
ponds or tanks, etc. The access to and identification of such facilities for speedy use
is fundamental for successful firefighting operations.
If the building has a fire hydrant(s) on its site, identification is required in order that
firefighters can locate the fire hydrant(s) quickly. A fire hydrant indicator plate (Figure
19) to British Standard BS 3251:1976 should be fitted at 450mm over the footpath
surface level.
Figure 18(b) Thumb-Lock
Figure 18(a) Panic Escape Device
49
The diameter of the water main in millimetres on the upper part of the plate and the
distance in metres of the marker from the fire hydrant on the lower part of the plate.
All the characters are black and the remainder of the front face should conform to
colour reference number 309 (Canary Yellow) of British Standard 381C.
Fire hydrants should be inspected and maintained in accordance with the
recommendations in Section 8, Table 2 Programme Maintenance Schedule, below.
6.12 Maintenance of Compartmentation (Fire Stopping)
Buildings are commonly divided into separate spaces called fire compartments and
separated from each other by fire resisting construction to limit the spread of fire and
smoke from one compartment to another. This is often done where parts of the
building are in separate uses, and to limit the size of individual compartments. In
buildings containing flats/apartments, each flat/apartment unit is a single fire
compartment. Care should be taken that building works do not affect
compartmentation.
In cases where damage to compartmentation is noted, repairs should be carried out
only by competent persons
Figure 19 Hydrant Markers
50
In buildings, services, pipes, ducts may pass through compartment walls or floors.
Special measures, known as fire stopping, are taken to ensure the fire resistance of
the compartmentation is maintained around these penetrations.
Typical fire stopping arrangements can be seen in Figure 20. Any fire stopping
works should be carried out by a competent person.
Figure 20 Fire Stopping of Pipe Penetration Wall
Figure 21 Service Risers in Common Areas
51
Fire stopping can be an issue in service risers. Service Riser cupboards are usually
located within the communal areas of buildings and contain pipework and cabling for
the main services provided to the building such as telephone, satellite television,
broadband, drainage, electricity and water. Figure 21 shows a typical riser door (fire
resisting), opening to the service riser with services. It is important that the service
riser doors are kept locked and secure when access to the riser is not required.
Risers should not be used for storage.
Fire /smoke dampers are active devices used in heating, ventilation, and air
conditioning (HVAC) ducts, to prevent the spread of fire and smoke inside the
ductwork through fire resistant walls and floors (Figure 22). When a rise in
temperature occurs, the fire/smoke damper closes, usually activated by a thermal
element which melts allowing springs to close the damper blades. Fire/smoke
dampers can also close upon receipt of an electrical signal from a fire alarm detector
and alarm system indicating the presence of heat or smoke in the building’s
occupied spaces or in the HVAC duct system.
Fire/smoke dampers should be inspected and maintained in accordance with the
recommendations in Section 8, Table 2 Programme Maintenance Schedule, below
Figure 22 Fire/Smoke Dampers
52
7 Buildings containing Flats/ Apartments
In buildings containing flats/apartments, the Section 18(2) responsibilities of the
person having control are likely to fall on the building owner or the Owners'
Management Company (OMC) or other organisation (see Section 3.0). The guidance
throughout this document will be of assistance in meeting these responsibilities. This
section contains additional information relating to buildings containing
flat/apartments.
In the case of OMCs, in order to have the capacity to meet their Section 18(2)
responsibilities they will require a reliable funding stream from service charges on
individual units. OMCs should set service charges at an appropriate level and
arrange timely collection of same, so that funding is available to maintain fire
protection facilities.
The person having control should review the arrangements for ensuring that
appropriate fire protection facilities are present within buildings containing
flats/apartments and are checked and maintained routinely, and behaviour which
could endanger fire safety or unacceptable practices by residents or others can be
prevented.
There is some additional information in respect fire safety in buildings containing
flats/apartments in “Guide to Fire Safety in Flats, Bedsitters and Apartments”
published by Department of Housing Local Government and Heritage. (See other
publications).
Residents of buildings containing flats/apartments should be provided with a copy of
the leaflet “Fire Safety in Flats and Apartments” issued by the Dept. of Housing Local
Government and Heritage, and available at the following link:
https://www.gov.ie/en/collection/4efe2-fire-safety-leaflets
53
7.1 Fire Detection and Alarm Systems
In buildings containing flats/apartments each flat/apartment should be an individual
compartment, and should be provided with early warning to occupants of the
flat/apartment through a domestic fire detection and alarm system. The
removal/disabling/failure to maintain domestic smoke alarms (or other actions or
behaviours which endanger fire safety) may be a breach of Section 18(3) of the Fire
Services Acts 1981 and 2003.
A separate fire detection and alarm system should be provided in common corridors
and stairways, supplemented by a heat detector and sounder inside each individual
flat/apartment entrance door. This fire detection and alarm system is designed to
give warning generally throughout the building (see Figure 23).
As noted above, Section 18(3) of the Fire Services Acts 1981 and 2003 places a
duty on each occupant to ensure that any person on the premises is not exposed to
danger from fire as a consequence of any act or omission on their part. Reasonable
access should be allowed to each flat/apartment for maintenance of the common fire
detection and alarm system.
Figure 23 Illustrative Fire Detection and Alarm System in a building containing
Flats/Apartments
54
7.2 Emergency Lighting System in Buildings with Open
Shared Balcony Egress
In buildings containing flats/apartments with open shared egress balconies,
emergency escape lighting should be provided along such routes to a final exit
leading to a place of safety.
7.3 Sprinkler Systems
Where sprinklers systems are provided in buildings containing flats/apartments
typically in open plan flats- there are maintenance requirements for these systems
(see Table 2 Programme Maintenance Schedule). Section 18(3) of the Fire Services
Acts 1981and 2003 places a duty on each occupant to ensure that any person on
the premises is not exposed to danger from fire as a consequence of any act or
omission on their part. Reasonable access should be allowed to each flat/apartment
for maintenance of individual sprinkler systems.
7.4 Smoke Control
In buildings containing flats/apartments, there are general provisions to remove or
dilute smoke in common corridors and stairways so as to keep them clear for escape
when required and for fire service intervention. Such smoke control systems can be
either natural openings directly to the outside (a window opening) or mechanically
assisted with motorised fans and smoke shafts.
Ventilation to remove smoke may be provided in either the stair lobbies or corridors
(Figure 24) that form the common access areas in buildings containing
flats/apartments, as well as in the staircase enclosure itself.
55
Where an automatic smoke control system is in place, and in the event of heat
and/or smoke entering the common areas, the smoke control system is designed to
vent the heat and smoke to allow for means of escape to continue to be safely used
and to facilitate the fire fighting activities.
In the case of a system design that employs a smoke shaft, if smoke is detected in
the common area, a fire/smoke damper (Figure 25) into the smoke shaft on only the
floor affected will open, together with the vent at the top of the shaft. This creates a
chimney effect, allowing the fire gases/ smoke to vent to open air, or may use
mechanical extract to vent the smoke. All other vents opening into the smoke shaft
should remain closed, to maintain the fire separation within the building, prevent
smoke spreading to other floors (Figure 25).
Figure 24 Corridor Automatic Ventilators to Smoke Shaft
56
7.5 Evacuation procedures
The person having control should ensure that each flat is provided with instructions
for the occupants as to how to react in the event of fire or alarm (see Appendix G). In
general, the appropriate response is to evacuate immediately to a place of safety
outside the building. Persons with disabilities may proceed to a designated refuge (a
place of relative safety within the building) and await assistance if required.
Figure 25 Sample mechanical smoke shaft system
57
7.6 Flat/Apartment Doors
The entrance door to individual flats/apartments from the common corridor/landing
forms part of the passive fire protection of means of escape in buildings containing
flats/apartments; such entrance doors should not be replaced with non-fire resisting
doors.
Flat/apartment entrance doors should be fire doors and should be inspected,
maintained and repaired on a regular basis to ensure that they operate
effectively.(see Table 2 Programme Maintenance Schedule, below).
7.7 Building Layout
Buildings containing flats/apartments can consist of many variations in size, height
and design, and include mixed uses and various ancillary areas. The mixed uses can
include commercial uses, such as shops, offices and assembly & recreation units.
Figure 26 Indicative Flat/Apartment configuration
58
The ancillary areas can include upper levels and/or basement carparks and/or plant
and storage areas. Figure 26 illustrates an indicative flat/apartment design with a
range of fire safety measures including active and passive systems. Not all
apartment buildings will include all the systems shown, as the presence of such
system(s) will depend on many factors, such as the height of building, the length of
common corridor and the provision of protected entrance halls (PEHs) inside
individual flats/apartments.
In buildings containing flats/apartments, each flat/apartment unit is a single fire
compartment. For this reason the carrying out of works in a building containing
flat/apartments is normally strictly controlled.
Figure 27 indicates different internal layouts inside a flat/apartment showing open
plan or entrance hall arrangements
Open Plan Flat/ Apartment Protected Entrance Hall Flat/ Apartment
Figure 27 Flat/Apartment Layouts
59
8 Recommended Routine Maintenance Schedules
A table of recommended routine maintenance schedules is presented for the typical
fire safety equipment and systems in buildings. The schedules are tabulated into
daily, weekly, monthly, and quarterly, bi-annual and annual activities. Many of the
daily, weekly and monthly activities can be carried out without expert knowledge of
the equipment or system and this is indicated by the green columns. The columns for
the quarterly, bi-annually and yearly activities should be carried out by persons who
have competency in their specific areas and can provide certification to the relevant
standard for the work carried out.
If information is required, the definitive maintenance requirements for all fire safety
equipment and systems should be sought from the equipment or system
manufacturers, suppliers, their technical advisers, and or specialised competent
contractors. It is important to restate that care should be taken to ensure competent
skilled contractors are employed to carry out fire safety equipment and systems
maintenance works. The contractor(s) tasked with works should be part of a
registered contractor’s association where relevant for their trade. The schedules
presented are recommended in the relevant guidance or standard appropriate for the
equipment or system.
Systems such as the electrical installation and gas installations should be subject to
periodic inspection and testing by a competent person, as recommended by the
appropriate standard such as Irish Standard I.S. 10101- National Rules for Electrical
Installations and Irish Standard I.S. 820 Non-domestic gas installations or Irish
Standard I.S. 813- Domestic gas installations.
60
Table 2; Maintenance Programme Schedule for Buildings
Regular Checks to be carried out by designated person
Planned inspection and maintenance to be carried out by a competent person
Maintenance Schedule for Active and Passive Fire Systems
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Escape
Routes
The following should be checked:
escape routes are not obstructed and
are immediately available for use;
escape routes should not be used for
storage;
electrical appliances for example,
tumble dryers , should not be located in
circulation spaces, common corridors,
lobbies ,stairways or landings .
Batteries or battery powered devices
should not be charged in circulation
spaces, common corridors, lobbies
stairways or landings
escape routes are clearly indicated,
sign-posted and adequately illuminated
the emergency lighting indicator in each
emergency light fitting is operative
final exit doors are capable of being
readily opened;
61
doors and gates across escape routes
should be easily and immediately
openable
curtains, drapes or hangings are not
placed across or along an escape route
in a manner which would impede or
obstruct escape;
mirrors are not placed across or along
an escape route or adjacent to an exit in
such a way as to confuse the direction
of escape;
floor coverings, rugs and mats are fixed
or laid so that they do not present a trip
or slip hazard during an evacuation, and
are not used to prop open doors;
fire resisting doors along escape routes
are kept closed at all times, unless they
are permitted to be fitted with hold-open
devices (for example, electro-magnetic)
designed to allow the door to close
upon activation of the fire detection and
alarm system
external areas at or near final exits are
kept free of obstructions, so as to allow
unimpeded escape to a place of safety
62
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Fire Detection
and Fire Alarm
Systems
I.S. 3218
All fire detection and fire
alarm systems should be
checked daily. In particular,
it should be ensured that:
a) the control and
indication panel
indicates normal
operation or, if any fault
is indicated, that it has
been logged and the
appropriate action(s)
taken;
b) any fault recorded the
previous day has
received attention.
All fire detection and fire alarm
systems should be checked weekly.
In particular, it should be ensured
that:
a) the control equipment is able to
receive a fire signal and to
initiate the evacuation procedure,
recording which trigger device
has been used, in accordance
with I.S 3218.
b) any standby batteries are in
good condition and the fuel, oil
and coolant levels of any
standby generators are correct,
topp
ing up as necessary.
See section
9.2.2.5 of IS
3218. A
Test/Servicing
certificate
should be
issued by the
competent
person upon
completion.
See section
9.2.2.6 of IS
3218. A
Test/Servicin
g certificate
should be
issued by the
‘competent
person’ upon
completion.
Emergency
and escape
lighting
systems
I.S. 3217
The minimum operational
requirements shall be
checked as set out in
section 16.2.1 of I.S. 3217
Additional checks to those
listed above may be
necessary, due to either the
type of system installed or
as a result of other factors.
In addition to the daily inspection
methodology, schedule and checklist
as detailed in 16.2.1, the following as
detailed in 16.2.2 of I.S. 3217 shall
be carried out on at least 25 % of the
emergency lighting system so that
100 % of the system is check at least
every 4 weeks.
a) visually check that each
emergency lighting lamp, in all
maintained type and or combined
(sustained) type emergency
luminaires, are operational and
illuminated.
b) in the case of all self-contained
and ATS (Type S) emergency
See 16.2.3 of
I.S. 3217 - In
addition to the
weekly
inspection
methodology,
schedule and
checklist
(16.2.2).
See section
16.2.4 of I.S.
3217.
Upon
completion of
the quarterly
inspection and
test, a report
for inspection,
testing and
servicing, as
detailed in
Annex Cl and
Annex C7 shall
be issued to
See
section
16.2.5 of
I.S. 3217.
Inspection
and testing
is carried
out once in
every 1
year
period
subsequen
t to the
completion
of 3 three
63
luminaires check that their LED
status indicators are illuminated
and showing healthy
condition/status,
c) ensure that all non-illuminating
lamps are replaced.
the owner or
occupier.
A copy of the
report shall be
placed in the
emergency
lighting
logbook.
The schedule
for periodic
inspections and
tests due dates
shall be
updated with
the required
information
(see Annex F
for model
schedule)
monthly
(quarterly)
inspection
s and
tests.
All
emergenc
y lighting
systems
shall be
tested to
their rated
duration.
64
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Sprinkler
systems
Commercial
Systems and
Residential
(Inside
apartments)
Systems
I.S. EN
12845
I.S. EN
16925
B.S. 8458
Domestic
Sprinkler
System
Maintenance
requirement
s in
accordance
with BS
9251: 2014 &
2021
Commercial Sprinklers
refer to Section 20 of I.S.
EN 12845 for
maintenance
Requirements
The installer shall provide
the user with a
documented inspection
and checking procedure for
the system. The
programme shall include
instruction on the action to
be taken in respect of
faults, operation of the
system, with particular
mention of the procedure
for emergency manual
starting of pumps, and
details of the maintenance
routines.
Residential Sprinklers
refer to Section 18 of I.S.
EN 16925 for
maintenance
Requirements
The Commercial sprinkler
system should be subject to a
weekly inspection and test as
detailed in Section 20.2.2 of
I.S. EN 12845: 2015+A1:
2019 by a competent person.
The Commercial
sprinkler system
should be subject
to a monthly
inspection and
test as detailed in
Section 20.2.3 of
I.S. EN 12845 by
a competent
person.
The
Commercial
sprinkler
system should
be subject to a
quarterly
inspection and
test as detailed
in Section
20.3.2 of I.S.
EN 12845 by a
competent
person.
The Commercial
sprinkler system
should be
subject to a half
annual
inspection and
test as detailed
in Section
20.3.3 of I.S. EN
12845 by a
competent
person.
The
Commercial
sprinkler
system should
be subject to a
half annual
inspection and
test as detailed
in Section
20.3.4 of I.S.
EN 12845 by a
competent
person.
The Domestic/
residential
sprinkler
system should
be subject to
an annual
inspection and
test as detailed
in Section 7.1.2
of BS 9251. by
a competent
person.
65
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Fire door
automatic
release
mechanism
s
EN 1155
All doors that are held
open by automatic
release mechanisms
should be released daily.
The operation of
hold-open
devices should
be tested once a
month by
simulating failure
of the mains
power supply or
operation of the
fire detection and
fire alarm
system.
The results of the
test should be
recorded.
Any doors that
are found to be
faulty should be
repaired or
replaced.
66
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Portable fire
extinguisher
s and fire
hose reels
I.S. EN 291
I.S. EN 671
Part 1
I.S. EN 671
Part 2
I.S. EN 671
Part 3,
I.S. EN 3
All gaseous, foam water and powder
extinguishing systems should be
checked weekly. In particular, it
should be ensured that:
a) any pressure gauges are
functioning correctly;
b) all operating controls are both
properly set and accessible;
c) all indicators are functioning
correctly;
d) the equipment, particularly
pipework and nozzles, is free
from dust and dirt, is not
physically damaged nor leaking,
and remains in its designed
position;
e) the fire risk and its enclosure
have not changed;
f) the quantity of extinguishing
medium is correct and for foam
systems, the water supply is
available and at the correct
pressure.
All points at which
portable fire
extinguishers or
hose reels are
usually located.
should be
checked monthly
Missing fire
extinguishers or
hose reels should
be replaced
immediately.(a
risk assessment
may recommend
more frequent
checks)
Fire Hose reels
should be visually
inspected once a
month.
In particular, it
should be ensured
that there are no
leaks and that
drum assemblies
are free to rotate
on their spindles
All portable fire
equipment
(PFEs) shall be
maintained in
accordance with
Clause 9 of I.S.
291 at intervals
not exceeding
12+/- 1 month.
All fire Hose
Reel equipment
shall be
maintained in
accordance with
Clause 6 of I.S.
EN 671 Part 3
annually.
Every 5 years all
fire hose reels
shall be
pressurized to
maximum
working
pressure
according to EN
671-1 and/or EN
671-2.
67
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Smoke
control
systems for
means of
escape and
fire-fighting
BS 7346-
8:2013
Smoke
Control
Association
Guidance
on Smoke
Control to
Common
Escape
Routes in
Apartments
Actuation of the system should be
simulated once a week. It should be
ensured that any fans and powered
exhaust ventilators operate
correctly, smoke dampers close (or
open in some systems), natural
exhaust ventilators open, automatic
smoke curtains move into position,
etc.
NOTE On large multi-zone
installations it might be
acceptable, with agreement from
the relevant authorities, to rotate
the equipment tested so that a
system is tested every week and
individual items are operated at
intervals of no more than three
months.
The actuation of
all smoke
control systems
should be
simulated once
every three
months.
All zones should
be separately
tested and it
should be
ensured that
any fans and
powered
exhaust
ventilators
operate
correctly, smoke
dampers close
(or open in
some systems),
etc.
Every 12
months, in
addition to
the
manufacture
r’s
recommend
ation and
weekly
tests, the
entire
system
should be
tested by
following the
original
acceptance
test
procedure.
A test
certificate
should be
issued.
68
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Fire hydrants/
Mains
IS 391
.
Arrangements
should be made
by the owners or
the occupiers to
ensure that, at
least twice a year,
maintenance is
carried out on all
private fire
hydrants by a
competent
person.
Periodic
inspections should
be made to
ensure that flow
and pressure
supplies have not
deteriorated.
Note: Periodic checks of the vicinity of all hydrants should be made to ensure that
there is no obstruction impeding accessibility (for example, shrubbery) and that
hydrant indicator plates are in position and clearly visible.
69
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Standby
Generators
B.S. 9991
Any standby generator
should be started up
once a month by
simulating failure of the
normal power supply,
and allowed to energize
the system for at least
1 h, while the system is
monitored for any
malfunctioning caused
by the use of the
generator.
After restoring the
normal supply, the
charging arrangements
for the generator
starting battery should
be tested, and the
appropriate action
should be taken if they
are found not to be
functioning correctly.
In addition, the oil and
coolant levels should
be topped up and the
fuel tanks filled.
70
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Fire Doors
BS 8214
6 Monthly(biennially in the case of flat/apartment
entrance doors)
Door Leaf
Does the door leaf sit against the door stop and is it free
from distortion? If the door is veneered or lipped, is the
glue still holding these products firmly in place? Is the door
free from damage including dents and holes? Door Frame
Is the door frame firmly attached to the wall? If a planted
door stop is present, is it firmly attached? Is the frame to
door leaf gap consistently 3mm? (tolerance of +/ 1mm)
Door Closers
Open the door to 5 degrees or 75mm. Does it close and
engage with the latch? Is the closer correctly attached to
the door and frame? Is the closer free from damage and
not leaking? If unlatched, does the closer hold the door in
line with the frame and intumescent seal? If hung in pairs,
do they close in line if both opened and released together?
Hold Open Devices
(only electronically powered allowed) Does the hold open
device release the door when required?
Lock and Latch Does the latch hold the door firmly in place
without rattling? Glazing and Glass Is the intumescent seal
continuous and attached to the glass and bead? Are the
glazing beads well attached to the frame and free from
damage? Is the glass free from damage and cracking? If
the glass has been replaced, is it fire rated glass? If glazing
71
Fire Doors
(continued)
panels are below 1500mm from the bottom of the door, is
the glass safety glass?
Threshold Gap
Is there a consistent gap under the door that allows it to
swing without touching the floor covering? Is the door to
floor covering gap consistently 10mm or less when the
door is closed?
Intumescent/Smoke/Acoustic Seals
Are intumescent seals in place?
Are the seals well attached inside the groove in the frame or
door leaf?
Are the seals continuous around the frame?
Are the seals free from damage?
If you have a brush or fin type seal, is it free from damage?
Hinges
Are there a minimum of 3 hinges with all the screws fitted?
Are all the screws the correct size? Are the hinges free from
metal fragments and oil leakage, which are signs of wear?
Are the hinges free from packing?
72
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Emergenc
y and
panic
escape
doors
I.S. EN
1125
Note: The operation of all emergency
and panic escape devices, especially
on external doors not used for other
purposes, should be checked
regularly for ease of operation and
opening of the door. Weather
conditions can affect the door and
frame relationship, and therefore the
ease of operation of escape devices.
To ensure performance the following
routine checks should be undertaken at
intervals of not more than one month (or
the period recommended by the producer;
a) Inspect and operate the panic exit
device to ensure that all components are
in a satisfactory working condition; using
a force gauge, measure and record the
operating forces to release the exit
device.
b) Ensure that the keeper(s) is (are) free
from obstruction.
c) Check that the panic exit device is
lubricated in accordance with the
producer’s instructions.
d) Check that no additional locking devices
have been added to the door since its
original installation.
e) Check periodically that all components
of the system are still correct in
accordance with the list of approved
components originally supplied with the
system.
f) Check periodically that the operating
element is correctly tightened and, using
a force gauge, measure the operating
forces to release the exit device. Check
that the operating forces have not
changed significantly from the operating
forces recorded when originally installed.
73
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Dry/Wet
Risers
I.S 391 2020
All fire mains should be
inspected every six months.
It should be ensured that:
a) for wet mains:
1) booster pumps and their
associated mechanical
and electrical apparatus
are functioning correctly;
storage tanks are full of
clean water
For dry fire mains, the tests
in 7.3.1 to 7.3.2 and 7.3.5.1.
of IS 391 should be carried
out annually.
For wet fire mains, the tests
in 7.4.2.1 and 7.5.3.1.1 of
IS 391
In addition the following
checks, should be carried
out
a) internal cleanliness,
condition and water level
of storage tanks,
including the operation
of float valves and any
water level alarms;
b) booster pumps and their
associated mechanical
and electrical equipment;
c) electrical supplies and
equipment to prevent
freezing;
d) operation of system
monitoring and alarms.
Where pressure
regulating valves are
installed
Note: Routine periodic visual checks of all fire main inlet and
landing valves should be carried out to deal with any
damage, and to ensure that all inlet and landing valve boxes
and/or riser cupboards are suitably secure and clear of
storage or debris. The person having control should consider
the frequency of these visual checks.
74
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Firefighti
ng Lift
I.S. EN
81-72
Operation of
the firefighters
lift switch to
check the lift
returns to the
fire service
access level,
parks with its
doors open
and that the lift
does not
respond to
landing calls.
The lift should
be connected
to the fire
detection
system.
Check to
ensure that the
lift responds to
the instruction
from the
detection
system.
Simulation
of a failure
of the
primary
power
supply to
check
changeover
to the
secondary
supply and
operation
from the
secondary
supply.
A full test of the firefighters lift operation
from the firefighters lift switch and the
fire detection system operation from the
secondary power supply to check the
full firefighting facilities including
communication systems. This should
check to ensure the lift can be driven to
any required floor and that on arrival at
a floor it only opens its door when
instructed to do so and then stays at the
floor with its doors open
Checks of building related issues
including measures to prevent water
ingress into the lift well and/ or
measures to address water ingress into
the lift well and the operation of any
pumps used to control the level of water
in the lift pit.
The lift maintenance contractor should
also advise of any need to change
components or parts of the lift to ensure
the availability and reliability of the lift in
the event of fire.
Advise of any change in standards
relating to lifts in service; particularly to
lifts for operation in the event of fire.
75
System
Daily
Weekly
Monthly
Quarterly
6 Monthly
Yearly
Fire /Smoke
Dampers
I.S. EN 15650
I.S. EN 15650 Ventilation for buildings
Fire & motorised Smoke/Fire dampers
Section 8.3 Note states: Regular testing
/inspection should be undertaken to meet
regulatory requirements, or at intervals not
exceeding six months. A comprehensive
example of the maintenance procedure is
given in Annex D of the standard. Some
automatic systems may allow more frequent
testing (48 h or less) and this may be required
by a national standard.
76
Appendix A. Referenced Standards
I.S. 3217 Emergency and escape lighting systems
I.S.3218:2013 Fire Detection and Fire Alarm Systems for Buildings-
System
+A1:2019 Design Installation Commissioning, Servicing And
Maintenance
I.S.EN 3 Portable Fire Extinguishers
I.S.EN 81-72 Safety Rules for the construction and maintenance of
Passenger lifts .Particular applications for passenger and
Goods lifts
I.S 391 2020 Fire mains for buildings - Installation, commissioning,
maintenance and testing
I.S.EN 1125:2008 Building Hardware - Panic Exit Devices Operated by a
Horizontal Bar, for Use on Escape Routes - Requirements
and Test Methods
I.S.EN 291:2015 Selection, commissioning, installation, inspection and
+A1:2022 maintenance of portable fire extinguishers and
Amendment 1
I.S.EN 671-1:2012 Fixed firefighting systems-Hose systems-Part 1: Hose
reels with semi rigid hose
I.S.EN 671 Part 2 Fixed firefighting systems-Hose systems-Part 2: Hose
systems with lay flat hose
I.S.EN 671 Part 3, Fixed firefighting systems-Hose systems-Part 3:
Maintenance of Hose systems with semi rigid hose and
hose systems with lay flat hose
I.S.EN 1155:1998/ Building Hardware - Electrically Powered Hold-Open
A1:2002 /AC: 2006 Devices for Swing Doors - Requirements and Test
Methods
I.S.EN 12845:2015 Fixed Firefighting Systems - Automatic Sprinkler
+AC: 2016+A1:2019 ,Systems - Design, Installation and Maintenance
(+AC: 2016) (+A1:2019)
77
I.S.EN 16282-7:2017 Equipment for commercial kitchens - Components for
+A1:2021 ventilation in commercial kitchens - Part 7: Installation and
use of fixed fire suppression systems.
I.S. EN 16925:2018 Fixed Firefighting Systems - Automatic Residential
& LC: 2018&AC: 2020 Sprinkler Systems - Design, Installation and Maintenance
BS 8214:2016 TC Timber based fire door assemblies. Code of Practice.
BS 9991:2015 Fire safety in the design, management and use of
residential
Buildings. Code of Practice.
BS 7346-8:2013 Components for Smoke and Heat Control Systems
Functional Recommendations and Calculation Methods
for Smoke and Heat Exhaust Ventilation Systems,
Employing
Steady-State Design Fires. Code of Practice
BS 9251:2021 Fire Sprinkler Systems for Domestic and Residential
Occupancies. Code of Practice
I.S. 3213:2020, Code of Practice for the storage of Liquid Petroleum Gas
Cylinders and cartridges.
British Compressed The storage of gas cylinders.Revision1:2022
Gases Association: CP44.
78
Appendix B. Legislation
Fire Services Acts 1981 and 2003
Fire Services Act, 1981, Number 30 of 1981
http://www.irishstatutebook.ie/eli/1981/act/30/enacted/en/html
Licensing of Indoor Events Act 2003, Number 15 of 2003
http://www.irishstatutebook.ie/eli/2003/act/15/enacted/en/html
Fire Safety in Places of Assembly (Ease of Escape), Regulations, 1985,
S.I. No. 249 of 1985
http://www.irishstatutebook.ie/eli/1985/si/249/made/en/print
Public Dance Halls Act 1935 to 2003
Building Regulations, 1997, S.I. No. 497 of 1997
http://www.irishstatutebook.ie/eli/1997/si/497/made/en/print?q=Building+Regul
a tions+1997
Building Control Act, 1990, Number 3 of 1990
http://www.irishstatutebook.ie/eli/1990/act/3/enacted/en/html?q=building+contr
ol+act
Building Control Act 1990 Revised Consolidated Law Reform Commission -
Updated to 1 November 2019
http://revisedacts.lawreform.ie/eli/1990/act/3/front/revised/en/html
Building Control Act, 2007, Number 21 of 2007
http://www.irishstatutebook.ie/eli/2007/act/21/enacted/en/html?q=building+cont
rol+act
Building Control Act 2007 Revised Consolidated Law Reform Commission -
Updated to 31 January 2019 - Consolidated
http://revisedacts.lawreform.ie/eli/2007/act/21/front/revised/en/html
79
Appendix C. Other Publications
Smoke Control Association - Guidance on Smoke Control to Common Escape
Routes in Apartment Buildings (flats and maisonettes). Revision 3.1 July 2020
The British Compressed Gases Association - CP44. The storage of gas
cylinders.Revision1:2022
80
Appendix D. Technical Guidance Documents
https://www.housing.gov.ie/housing/building-standards/tgd-part-d-materials-and-
workmanship/Technical-guidance-documents
Guides for fire safety, made under Section 18A of Fire Services Acts 1981 and 2003,
DoEHLG (DHLGH) NDFEM from 1989 to 2019.
81
1989 Code of Practice for the Management of Fire Safety in Places of Assembly
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad,8
15,en.pdf
1989 Guide to Fire Precautions in Existing Hotels, Guesthouses and Similar
Premises
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad, 1
4964,en.pdf
1994 Guide to Fire Safety in Flats, Bedsitters and Apartments (Existing)
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad%
2C1024%2Cen.pdf
1996 Guide to Fire Safety in Existing Nursing Homes and Similar Type Premises
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad,8
20,en.pdf
1998 Code of Practice for Fire Safety and Indoor Concerts
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad%
2C18105%2Cen.pdf
1998 Guide to Fire Safety in Fire Safety in Hostels
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad,1
026,en.pdf
1999 Guide to Fire Safety in Fire Safety in Preschools
https://www.earlychildhoodireland.ie/wp-content/uploads/2015/08/Fire-Safety-
In-Preschools.pdf
1999 Guide to Fire Safety in Guest Accommodation
https://www.housing.gov.ie/sites/default/files/migrated-
files/en/Publications/Community/FireandEmergencyServices/FileDownLoad,2
072,en.pdf
2008. Guidance document on fire safety in stores for explosives published by
Department of Housing Local Government and Heritage.
2017 Code of Practice for Fire Safety in New and Existing Community Dwelling
Houses
82
https://www.housing.gov.ie/sites/default/files/publications/files/code_of_practic
e_for_fire_safety_in_community_dwelling_houses_2017_0.pdf
2019 Guide to Fire Safety in Existing Traveller Accommodation
https://www.housing.gov.ie/sites/default/files/publications/files/guide_to_fire_
safety_in_existing_traveller_accommodation_final_november.pdf
Guidance-Note on Periodic Inspection and Testing of Electrical Installations
required by the 2007 Safety Health and Welfare at Work (General Application)
Regulations
2022 Code of Practice for fire Safety Assessment of Premises and buildings
https://www.gov.ie/en/publication/354c8-code-of-practice-for-fire-safety-
assessment-of-premises-and-buildings
83
Appendix E. Management Responsibilities - Exemplar
Premise (Informative)
84
Appendix F. Requirements for Landlords
85
Requirements for Landlords (Continued)
86
Appendix G. Instructions for Residents
Instructions for escape in the event of fire should be posted on the back of each
apartment entrance door. The instructions should also include a floor plan and the
following information
the action to be taken in the event of fire
the action to be taken on discovering a fire or hearing the fire alarm
the procedure for calling the fire service
the location of all relevant escape routes from the building (on the floor plan)
the location of fire alarm call points and the fire alarm control panel(s)
the location of firefighting equipment
Firefighting equipment should never be mishandled or tampered with. Fire doors
should not be modified, tampered with, or propped open within the common areas of
accommodation blocks. Fire alarm sounders, heat sensors as parts of the common
alarm system are installed in each residential unit, typically just inside the flats
entrance door. These systems are tested on a quarterly basis and access is required
for this purpose. Residents should allow the t contractors acting for the Owners’
Management Company reasonable access to the accommodation to carry out fire
safety preventive maintenance.
Residents must not interfere with the fire protection system and equipment, for
example, by; removing safety equipment propping fire doors open, covering or
removing smoke detectors, blocking escape routes with furniture, bicycles or rubbish
etc.
The most important steps that the Residents can take to minimise the risk of a fire are:
1. Make sure that heaters are located where they will not set fire to
curtains, bedding or furnishings.
2. Do not use portable gas or paraffin heaters in the apartments.
3. Do not store highly flammable materials in the apartment (such as
paint, thinners, LPG cylinders, paraffin or petrol).
4. Do not store large quantities of combustible materials.
5. Residents should understand the dangers of:
smoking in bed or when drowsy
careless use of candles or incense sticks
overloading electrical sockets
having trailing cables
leaving a chip pan or frying pan unattended, or over-full of oil
87
placing clothes to dry on or too close to heaters
Residents should practice ‘the bedtime fire safety routine’, which should include
the following actions;
ensuring the cooker is turned off
unplugging electrical appliances
making sure that no cigarettes or candles are left burning
closing all doors
In the event of an outbreak of a fire, residents should;
Not attempt to fight fires that have already taken hold: evacuate from the
dwelling. Sound the common alarm as you make your escape
Telephone the Fire Service on 999 or 112 immediately from a place of
safety
Not try to rescue belongings or pets
Appendix H. Instructions for Occupants
88
Appendix J. Check Sheets/Log Sheets/Certification of
Equipment and Systems
Every apartment building, relies on the health of its fire safety equipment and systems.
The use of check sheets, log sheets are important tools to help in the maintenance
process. There are also useful records and demonstrate work carried out on
equipment and systems
Appendix J 1 Emergency Lighting Log Sheet
89
Appendix J 2 Emergency Lighting Check List
90
Appendix J.3 Certification of Smoke Control System
91
Appendix J.4 Certification of Fire Detection and Alarm System
92
Certification of Fire Detection and Alarm System (continued)
93
Certification of Fire Detection and Alarm System (continued)
94
Certification of Fire Detection and Alarm System (continued)
95
Appendix J 5 Portable Fire Extinguisher Check Sheet
96
Portable Fire Extinguisher Check Sheet (Continued)
97
Appendix J.6 Registered Gas Installers Ireland (RGII) Certificate
98
Registered Gas Installers Ireland (RGII) Certificate (Continued)
99
Appendix K. Nomenclature / Abbreviations/ Definitions
- PHC- Person Having Control
- FSA Fire Services Act
- DHLGH - Department of Housing, Local Government and Heritage
AOV (automatically opening vent): A vent provided for smoke control in common
parts, which opens automatically when smoke is detected by smoke detectors.
Active Protection: Active protection are those systems which come into action on
detection of fire e.g. fire detection and alarm system, automatically opening vent.
Circulation Space: A space (including a stairway) mainly used as a means of
access between a room and an exit from the building.
Compartmentation: Sub-division of a building by fire-resisting walls or floors
normally for the purpose of limiting fire-spread within the building.
Dry Riser: A dry riser is a normally empty pipe that can be externally connected to a
pressurised water source by firefighters. It is primarily a vertical pipe, although there
can be horizontal sections, intended to distribute water to multiple levels of a building
or structure
Emergency Escape Lighting: Lighting that provides illumination for the safety of
people leaving the building when the normal lighting fails.
Escape Route: Route forming part of the means of escape from any point in a
building to the final exit. .
Apartment, "flat": means separate and self-contained premises constructed or
adapted for residential use and forming part of a building from some other part of
which it is divided horizontally - quoted from BUILDING CONTROL REGULATIONS
1997 - SI 497 of 1997.
Final Exit: The termination of an escape route from a building giving direct access to
a street, passageway, walkway or open space and sited to ensure the rapid
dispersal of persons from the vicinity of a building so that they are no longer in
danger from fire and/or smoke.
100
Fire Compartment: A part of a building constructed to prevent the spread of fire to or
from another part of the building.
Fire Damper: Mechanical or intumescent device within a duct or ventilation opening,
which is operated automatically in the event of fire, to prevent the passage of fire.
(Where there is a need to prevent the passage of smoke, the fire damper needs to
satisfy additional criteria.)
Fire Main: Water supply pipe installed in a block of flats for fire-fighting purposes,
fitted with landing valves at specific points. The main may be ‘dry’, in which case it is
fitted with inlet connections at fire and rescue service access level, so that it can be
charged with water from pumping appliances. In tall blocks, the main is ‘wet’ and is
permanently charged with water from a pressurised supply.
Fire Stopping: A seal provided to close an imperfection of fit or design tolerance
between elements or components, to restrict the passage of fire and smoke.
Fire Door: A door, together with its frame, hinges, latches, hardware, glazing,
automatic self-closing device provided for the passage of people, which, when
closed, is intended to restrict the passage of fire and smoke to a predictable level of
performance.
Intumescent strip/seal: This is a piece of material fitted around a doorway that
when exposed to heat, expands closing any gaps around the door to stop the fire
spreading for a period of time. Intumescent strips usually come with either 30 or 60
minutes of resistance to fire.
Means of Escape: A route(s) provided to ensure safe egress from the premises or
other locations to a place of total safety.
Multi-Unit Building: A building containing 2 or more dwellings and using a common
entrance.
Owners’ Management Company (OMC): A not-for-profit company established for
the management of a Multi-Unit Development. It owns the common areas of the
estate. It is collectively owned and controlled by all the owners of the properties
within the estate. The directors are elected by the OMC members, and are typically
unpaid volunteers.
101
Passive Protection: Passive protection relates to the defence against fire provided
by the fabric and construction of a building.
Protected Stairway: A stairway that is adequately protected from the rest of the
building by fire-resisting construction.
Riser: A cupboard located within the communal areas of apartment buildings which
contain cabling for the main services provided to the individual apartments. For
example: telephones satellite television, electricity etc.
Smoke Alarm: Device containing within one housing all the components, except
possibly the energy source, for detecting smoke and giving an audible alarm.
Smoke Control System: This is a system that is used to limit the migration of
smoke within a building due to a fire. There are several methods to limit this
migration, and some are designed to provide a tenable environment for occupants to
egress the building.
Storey: Any of the parts into which a building is divided horizontally above or below
ground level.
Wet Riser: A Wet riser is a supply system intended to distribute water to multiple
levels or compartments of a building, as a component of its firefighting
102
gov.ie/housing
The Department of
Housing, Local Government and Heritage