Unrestricted
Frequently asked questions 11/2018
Several methods to prevent G120 inverter
parameters from being modified by mistake
G120 parameter error modification
https://support.industry.siemens.com/cs/cn/zh/view/109762582
Unrestricted
2
Copyright
ã
Siemens
AG Copyright year
All rights reserved
Catalog
1 Method of locking the keys on BOP-2 panel ...................................................... 3
2 Method of activating the write protection function of frequency conversion ...... 4
3 Method of activating G120's proprietary technology protection function through
"STARTER" software .................................................................................................. 5
3.1 Create a special list that does not belong to the protection
of proprietary technology ................................................................................... 5
3.2 Activate the proprietary technology protection function of G120 ......... 5
3.3 Cancel proprietary technology protection function ............................ 6
3.4 Modify the password of proprietary technology protection ................. 7
4 Method of activating G120's proprietary technology protection function through
IOP panel .................................................................................................................. 8
4.1 Create a special list that does not belong to the protection of propri-
etary technology with IOP .......................................................................................... 8
4.2 Activate the proprietary technology protection function of G120 with IOP
................................................................................................................................ 8
4.3 Cancel proprietary technology protection function with IOP ............ 10
4.4 Modify the password of proprietary technology protection with IOP
....................................................................................................................................10
5 Comparison of several methods to prevent G120 parameter from being
modified by mistake ..................................................... 12
Unrestricted
3
Copyright
ã
Siemens
AG Copyright year
All rights reserved
1 Method of locking the buttons on the BOP-2
panel
Press and hold the ESC + OK key on the BOP-2 panel for more than 3
seconds until the panel displays LOCKED, indicating that the panel has been
locked. To unlock, press and hold the ESC + OK key for more than 3 seconds .
When the panel displays UNLOCKED, it indicates that the panel has been
unlocked. This function only locks the function of modifying parameters
through this panel. Parameters can still be changed by using "STARTER"
software or other methods.
<Figure 1-1 BOP-2 Panel locking interface>
Unrestricted
4
Copyright
ã
Siemens
AG Copyright year
All rights reserved
2 Method of activating the write protection
function of frequency converter
By modifying the parameter p7761-1, the write protection function
of frequency converter can be activated. After activating the write
protection of frequency converter, the original parameters will change
(as shown in Figure 2-1, p1120 changes to r1120). So the original P
parameter cannot be modified. If p7761=0 is set again, the write
protection function of frequency converter can be cancel.
<Figure 2-1 P1120 changes to r1120>
Note: activating the write protection function of the inverter can be
cancel by restoring the factory settings, but all the parameters set
before will be cleared.
Unrestricted
5
Copyright
ã
Siemens
AG Copyright year
All rights reserved
3 Method of activating the proprietary tech-
nology protection function of G120
through "STARTER" software
The proprietary technology protection function of G120 can not only protect
our set parameters from being modified, but from being copied by others. Let's
introduce this function:
3.1 Create a special list that is not within the scope of
proprietary technology protection
In order to facilitate G120 maintenance in the future, we can cre-
ate a parameter list before activating the proprietary technology pro-
tection function. After the proprietary technology protection func-
tion is activated, the parameters in this list can still be read and
written.Customers can list the parameters that they want the mainte-
nance personnel to adjust. In the factory setting, only the password
p7766 protected by proprietary technology is include in the special
list.
First, we use STARTER to connect G120. Then click and save it,
offline.Determine the number of parameters required by the special
list by modifying the parameter p7763, then save it and enter the on
line mode. Click and download to G120. After downloading, online,
you can get the corresponding number of subscripts in parameter p7764,
and then input the number to be protected into p7764
As shown in Figure 3-1, set p7763 to 5, and then there will be five
subscripts from p7764[0]-p7764[4] in p7764, so you can set five parame-
ters here.
< Figure 3-1 special case list parameter table >
Special attention should be paid here: If the password p7766 is
deleted from the special list, the password for proprietary technol-
ogy protection cannot be entered or modified. The setting parameters
of G120 can only be accessed again by drinking the factory setting of
G120. When the factory setting is reset, the configuration in G120
will be lost, and G120 must be debugged again.
3.2 Activate the proprietary technology protection
function of G120
After we have completed the debugging of G120 and successfully
created the special list of proprietary technology protection, we
can activate proprietary technology protection function of G120.
Unrestricted
6
Copyright
ã
Siemens
AG Copyright year
All rights reserved
<图 3-2 starter 激活专有技术保护界面><Figure 3-2 STARTER activate
proprietary technology protection interface>
a) In the pop-up dialog box, as shown in Figure 3-3, the first
option, that is, by default, does not have copy protection.
b) If our G120 is configured and inserted with SD card, we can
choose one with basic copy protection function (bound to memory
card) and another with extended copy protection function (bound
to memory card and control unit)
c) If you want to enable the diagnostic function when the
proprietary technology protection is activated, you can
activate the option "enable diagnostic function".
d) Click Specify to enter the password, and select Copy RAM to
ROM, save it permanently, and finally click OK, so that the
proprietary technology protection function is activated.
First, use STARTER software to connect the G120 device online, and
right-click the mouse on the CU unit, as shown in Figure 3-2, and
select Drive unit know-now protection, and then select Active.
Unrestricted
7
Copyright
ã
Siemens
AG Copyright year
All rights reserved
If you select temporary, that is to say, after the power is
restarted, the proprietary technology protection function of G120 is
still effective. If you select permanent and click "Copy RAM to ROM",
G120 will delete the password and cancel the proprietary technology
protection function.
After selection, enter the correct password in the "Password" and
click the "OK" button to cancel the proprietary technology protection
function.
<Figure 3-4 STARTER activate proprietary technology protection password
cancel interface>
3.4 Modifying the password for proprietary technology
protection
Connect G120 device online. In the drive unit know-how protection
menu, select change password to modify the password.
For more information on the protection of the know-how of G120, you
can view the introduction to know how protection is in selection 7.6
of the G120 perating manual or click the link below to view more
details.
http://www.ad.siemens.com.cn/download/docMessage.aspx?ID=6852
<Figure 3-3 STARTER activate proprietary technology protection password
setting interface>
3.3 Cancellation of proprietary technology protection func-
tion
Connect the G120 device online, right-click on the CU unit, select
"Drive unit know-how protection" in the pop-up dialog box and select
"De-activate" from the menu, and then the menu as shown in the figure 3-
4 will pop up.
Copyright
ã
Siemens
AG Copyright year
All rights reserved
4 Method of activate the proprietary tech-
nology protection function of G120 by
IOP panel
The proprietary technology protection function of G120 can not
only be activated by STARTER software, but also be activated by the
IOP panel to protect the parameters we set from being modified and
checked. Here we will introduce this function:
4.1 Using IOP to create a special list that does not
belong to the scope of proprietary technology protection
First, we use IOP to select "Menu" from the main screen, as shown
in Figure 4-1, and then click "search by number" as shown in Figure
4-2. Then input 7763, click "OK", and enter p7763 parameter. By
modifying the value of parameter p7763, we can determine the number
of parameters required in the special list, and then select parameter
p7764 to input the special parameter into p7764.
<Figure 4-1 IOP key interface>
<Figure 4-2 parameter display interface>
Special attention should be paid here: if the password p7766 is
deleted from the special list, the password of proprietary
technology protection can no longer be entered or modified. You
must restore the factory settings of G120 before you can access the
setting parameters of G120 again. When the factory settings are
restored, the configuration in G120 will be lost and the G12 must
be debugged again.
Unrestricted
8
Unrestricted
9
Copyright
ã
Siemens
AG Copyright year
All rights reserved
First step To complete the configuration of proprietary
technology protection
Get to the parameter p7765 according to the above method. For
the meaning of parameter p7765, see the following figure:
<Figure 4-3 the meaning of parameter p7765>
If G120 is configured and inserted with SD card, you can choose
to set bit 0 to 1. Select the function with extended copy protection
(binding memory card and control unit), or you can choose to set bit
1 to 1 and select the function with basic copy protection (binding
memory card only). If you want to allow the use of G120 diagnostic
and monitoring curve functions, you need to set bit 2 to 1.
Step two Enter a new password
Get to the parameter p7767. There are 0-29, 30 subscripts in
p7767. When setting, enter according to ASC code comparison ta-
ble (see the figure below). The default value in each subscript
is 42, which means "*". p7767[29] needs to be set to 0 after
password input, indicating that password input is completed.
4.2 Using IOP to activate the proprietary technology pro-
tection function of G120
After we have completed the debugging of G120 and successfully
created the special list of proprietary technology protection, we can
activate the proprietary technology protection function of G120.
Unrestricted
10
Copyright
ã
Siemens
AG Copyright year
All rights reserved
<Figure 4-4 ASC code comparison table>
For example: enter the password "MaC", as shown in Figure 4-4,
P7767[0]=77, P7767[1]=97, P7767[2]=67. Finally, let P7767[29]=0,
and then the new password is successfully entered.
Step three Confirm the new password and activate the proprietary
technology protection function
According to the above method, enter the same value in P7768 pa-
rameter as in P7767 parameter, and when P7768[29]=0 is set, the
password is confirmed and the proprietary technology protection
is successfully activated. After successfully activation, the
icon will appear on the IOP panel, as shown in Figure 4-5.
For example: input P7768[0]=77, P7768[1]=97, P7768[2]=67. Fi-
nally, let P7768[29]=0 and the proprietary technical protection
function is activated.
Unrestricted
11
Copyright
ã
Siemens
AG Copyright year
All rights reserved
Details of proprietary technology protection using IOP to activate
G120 can be found in section 7.9 of the IOP manual.
https://support.industry.siemens.com/cs/us/en/view/109736312/zh
Note to activate the proprietary function, IOP-2 setting method is
the same as IOP.
4.3 Cancel proprietary technology protection function
with IOP
Get to the parameter P7766 and enter the correct password in
p7766. Finally, set P7766[29]=0. When it is confirmed, the protection
function of proprietary technology is canceled. But it should be
noted that this is only temporary cancellation. After the device is
powered off and powered on again, the proprietary technology protec-
tion is still activated. If you want to cancel completely, you need
to enter the correct password in P7766, then delete the password in
P7767, set the corresponding parameter value to 0, delete and confirm
the password in P7768, then the proprietary technology protection is
completely canceled. For example, P7767[0]=0, P7767[1]=0, P7767[2]=0,
P7767[29]=0. P7768[0]=0, P7768[1]=0, P7768[2]=0, P7768[29]=0.
4.4 Modifying the password protected by proprietary tech-
nology with IOP
Get to the parameter P7766 and enter the correct password. Then en-
ter the new password in P7767 and confirm it in P7768. At this time,
the new password takes effect.
Note that the proprietary technology protection function of G120
activated by STARTER software and activated by IOP panel are inter
connected. The essence of its modification falls into the correspond-
ing parameters. Therefore, the proprietary technology protection func-
tions activated in any way can be canceled and password modified
through IOP or STARTER.
<Figure 4-5 Activation interface of proprietary technology protection>
Unrestricted
12
Copyright
ã
Siemens
AG Copyright year
All rights reserved
5 Comparison of several methods to prevent
G120 parameter from being modified by mistake
1) Set BOP-2 to prevent parameters from being modified by mistake.
This method is relatively simple to operate, but the protection level
of this method is relatively low. Other people can modify parameters
by using software and other methods.
2) Activation of write protection to prevent parameters from being
modified by mistake. This method is relatively simple in operation
and comprehensive in protection, but its security level is not
enough.
3) Compared with the other two methods, this methods has the highest
protection level. If the customer has an SD card, it can also bind
the corresponding SD card to prevent the parameters from being copied
by others. The function can be activated through STARTER software or
IOP panel. Activation with STARTER software is more convenient and
fast, while using IOP panel is relatively complex and the operation
is more complicated.